Honeywell UMC800 Reference Manual page 134

Rs232 communications
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Parameter Index Reference
use_rpm
33
sp_rate_dn
34
sp_rate_up
35
RATIO
37
LBIAS
38
devbar_hi
39
devbar_low
40
deadband
43
124
BOOL
Use minutes (0) or repeats per minute (1) for integral constant
REAL
Set point low rate of change limit, 0 (off) to 99999 (eu/min)
REAL
Set point high rate of change limit, 0 (off) to 99999 (eu/min)
REAL
Gain value for Ratio PID (-20 to 20) (default 1) [ used when RA_BIAS
> 0]
REAL
Bias value for Ratio PID when RA_BIAS = LOC_BIAS](-99999 to
99999) (0)
REAL
High scale value for deviation bar graph (0 to 99999) (default 100)
REAL
Low scale value for deviation bar graph [always = -devbar_hi]
REAL
adjustable gap between forward and reverse motor operation (.5 to 5%)