Advertisement

5.12 ASYS Function Block

Description
The Analog System Status Block (ASYS) is a function block and is part of the Alarm/Monitor category. It
provides read access to controller status values including those related to the Analog execution cycle. The
output may be connected to function block inputs. The outputs may also be connected to signal tags for
operator interface monitoring. The ASYS System Monitoring block is assigned block number 249. It looks
like this graphically on the Control Builder:
Dynamic Parameters:
Parameter
Index
status
0
CYC_CNT
1
EXCTIME
3
PK_EXCTIME
4
EXECFAULT
7
CYCTIME
8
CYCMINS
9
NEWSTART
10
RESTART
11
ALM_ACTIV
12
ALM_UNACK
13
HWOK
14
LOWBTRY
15
HITEMP
16
8/99
Analog function block scan cycle time in sec.
Analog function block scan cycle time in min.
Logic 1 (Hi) for one analog scan cycle after a new start of program (Program to Run)
Logic 1 (Hi) for one analog scan cycle after power up
Logic 1 (Hi) if there is any operator panel alarm is present
Logic 1 (Hi) if there is any operator panel unacknowledged alarm present
Logic 1 (Hi) if a hardware fault is detected
Logic 1 (Hi) if battery is low
Logic 1 (Hi) if internal temperature is too high (>70C)
Logic 1 (Hi) if there is a comm. failure to the operator interface
Logic 1 (Hi) if a function block fails to operate properly
Logic 1 (Hi) when the controller run/program/test switch is in the test mode
Time controller was off (in sec.) after power loss (available for one analog scan cycle)

Table 5-15 ASYS Dynamic Parameters

Type
Use
R/W
REAL
C
R
REAL
C
R
REAL
C
R
REAL
C
R
BOOL
C
R
REAL
O
R
REAL
O
R
BOOL
O
R
BOOL
O
R
BOOL
O
R
BOOL
O
R
BOOL
O
R
BOOL
O
R
BOOL
O
R
RS232 Communications Reference Manual
Function Parameter Index Reference
Description
block status (see section 5.2 for code list)
number of control block cycles
control block execution time in seconds
peak control block execution time in seconds
ON = executive fault
control block cycle time in seconds
control block cycle time in minutes
ON = new start
ON = warm start
ON = active alarm
ON = unacknowledged alarm
ON = no hardware faults (See note 6)
ON = battery is low
ON = high RJ temperature
49