5.72 VLIM Function Block
Description
The VLIM label stands for Velocity (Rate) Limiter. This block is part of the Auxiliary category. It looks
like this graphically on the Control Builder.
Dynamic Parameters:
Parameter
Index
Type
status
0
REAL
OUT
1
REAL
H
2
BOOL
L
3
BOOL
X
4
REAL
EN
5
BOOL
Static Configuration Parameters:
Table 5-96 VLIM Static Configuration Parameters
Parameter
Index
Type
irate
0
REAL
drate
1
REAL
8/99
Table 5-95 VLIM Dynamic Parameters
Use
R/W
Description
C
R
block status (see section 5.2 for code list)
O
R
primary output
O
R
high rate limit indication
O
R
low rate limit indication
I
R
primary input
I
R
enable input
Description
increase rate limit (eu/min, >=0) {0 to 99999}
decrease rate limit (eu/min, >=0) {0 to 99999}
RS232 Communications Reference Manual
Function Parameter Index Reference
127