5.60 STSW Function Block
Description
The STSW label stands for the Setpoint Scheduler State Switch. This block is part of the Setpoint
Scheduler category. It looks like this graphically on the Control Builder.
Dynamic Values:
Parameter
status
STRQ
JOG
GHOLD
RESET
HOLD
RUN
ADV
Static Configuration Values
None
8/99
Table 5-80 STSW Dynamic Values
Index
Type
Use
0
REAL
C
1
REAL
O
2
BOOL
I
3
BOOL
I
4
BOOL
I
5
BOOL
I
6
BOOL
I
7
BOOL
I
RS232 Communications Reference Manual
Function Parameter Index Reference
R/W
Description
R
block status
R
Encoded state request output
R
OFF to ON requests jog state
R
ON = guaranteed hold state
ON to OFF and previous state was Run, then return
to RUN mode
R
OFF to ON requests reset state
R
OFF to ON requests hold state
R
OFF to ON requests run state
R
OFF to ON requests advance state