5

GENERAL REQUIREMENTS

Biasi UK Ltd support the Benchmark initiative.
The Benchmark Log Book is located at the back
of this manual and should be completed by the
Installing/Commisssioning
handed over to the User for future reference by
other visiting Engineers. Also included is the
Service Interval Record card that should be
completed by the Service Engineer following
the annual service maintenance of the boiler
and system.
This appliance must be installed by a compet-
ent person in accordance with the Gas Safety
(installation & Use) Regulations.
5.1

Related documents

The installation of this appliance must be in ac-
cordance with the relevant requirements of the
current Gas Safety (Installation & Use) Regula-
tions, the Local Building Regulations, the current
I.E.E. Wiring Regulations, the Regulations and
by--- laws of the local water undertaking, and in
Scotland, in accordance with the Building Stan-
dards (Scotland) Regulation. Health and safety
document n° 635 "Electricity at work regs.".
It should also be in accordance with the British
Standard Codes of Practice:
5.2

Location of appliance

The appliance may be installed in any room or in-
ternal space, although particular attention is
drawn to the requirements of the current I.E.E. Wir-
ing Regulations, and in Scotland, the electrical
provisions of the Building Regulations applicable
in Scotland, with respect to the installation of the
combined appliance in a room containing a bath
or shower.
Where a room---sealed appliance is installed in
a room containing a bath or shower, any electri-
cal switch or appliance control, utilising mains
electricity should be so situated that it cannot
be touched by a person using the bath or
shower.
The location must permit the provision of an ad-
equate flue and termination.
For unusual locations special procedures may be
necessary and BS 6798 gives detailed guidance
on this aspect.
A compartment used to enclose the appliance
must be designed specifically for this purpose.
18
This appliance is not suitable for external installa-
tion.
Engineer
and
The provision for satisfactory flue termination must
be made as described in BS 5440 part 1.
The appliance must be installed so that the flue ter-
minal is exposed to external air.
It must not be installed so that the terminal dis-
charges into an other room or space as an out-
house or lean--- to. It is important that the position
of the terminal allows a free passage of air across
at all times.
The terminal should be located with due regard for
the damage or discoloration that might occur to
building products in the vicinity.
In cold and/or humid weather water vapour may
condense on leaving the flue terminal; the effect of
such "steaming" must be considered.
The minimum acceptable spacing from the ter-
minal to obstructions and ventilation openings are
specified in Fig. 5.1.
Fig. 5.1
A
B
C
D
E
F
G
H
I
J
K
5.3

Flue system

BC
F
D
HI
J
A
Terminal position
.
Directly below a window or other opening
.
Below gutters, soil pipes or drain pipes
.
Below eaves
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Below balconies or car port roof
.
From vertical drain pipes and soil pipes
.
From internal or external corners
.
Above ground or balcony level
.
From a surface facing a terminal
. .
From a terminal facing a terminal
.
From an opening in the car port
(e.g. door, window) into dwelling
.
Vertically from a terminal in the same wall
rev. 17.09.93
M
F
N
G
E
L
K
G
mm
. . .
300
. . . . .
75
200
. . . . . . . . . .
650*
. . . . .
75
. . . . . . . . . .
300*
. . . . . . . . . . . .
300
. . . . . . . . . . .
600
. . . . . . . . .
1 200
. . . . . . . . .
1 200
.
1 500