Horizontal Terminations; Rigid Pipe 4" X 6-5/8" (102Mm X 175Mm) - Regency GF900L-NG Owners & Installation Manual

Gf900l series gas fireplace
Hide thumbs Also See for GF900L-NG:
Table of Contents

Advertisement

The diagrams below shows examples of horizontal termination arrangements using one 90
o
1) A maximum of one 90
elbow is permitted.
2) Minimum distance between elbows is 1 ft. (305mm).
Maintain clearances to combustibles as listed in the "Clearances" section.
Horizontal vent must be supported every 3 feet.
Firestops are required at each fl oor level and whenever passing through a wall.
Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems.
A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.
Flex system can only be used up to 3m - otherwise rigid venting must be used.
Regency GF900L Gas Fireplace

HORIZONTAL TERMINATIONS

" (
RIGID PIPE 4" X 6-5/8
Straight Out Horizontal Venting
Diagram 1
center
of hole
C L
Please note the minimum centerline for
basic install shown above.
102MM X 175MM)
o
elbow.
C L
INSTALLATION
21