VENTING ARRANGEMENT FOR VERTICAL TERMINATIONS
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two
o
45
elbow, with Rigid Pipe Venting Systems.
•
Vent must be supported at offsets.
•
Minimum distance between elbows is 1 ft. (305mm).
•
Maintain clearances to combustibles as listed in the
"Clearances" section.
•
Horizontal vent must be supported every 3 feet.
•
Firestops are required at each fl oor level and whenever
passing through a wall.
•
Must use optional rigid pipe adaptor (Part# 510-994)
when using rigid pipe vent systems.
•
Refer to the "Vent Restrictor Position" section for details
on how to change the vent restrictor from the factory
setting of Set 0 to Set 1 or Set 3 if required.
"THIS UNIT MUST ALWAYS
TERMINATE / VENT
DIRECTLY TO THE OUTDOORS."
Regency GF900L Gas Fireplace
Vertical Venting with One(1) 90
o
Elbows (1 - 90
o =
2 - 45
N
OTE: For ULPG vent restrictor -
Set to "0" - 75mm open.
Restrictor Set #3
18mm open
INSTALLATION
o
)
23