18

Top Vent Configuration with Vertical Termination

Use 6-5/8" Diameter Vent
Horizontal sections require a ¼" (6mm) rise every 12" (305mm) of travel.
A maximum of four (4) 45° or 90° elbows may be used. Of these elbows, only one (1) may be a
horizontal elbow (see illustration).
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
and diffuser position. NOTE: Restrictor positions are based upon lab tests. The ideal restrictor
position may vary slightly, especially when the termination is near a demarcation line.
© Travis Industries
Installation
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
Horizontal elbows are elbows placed between
two horizontal sections of pipe. One 45° or 90°
horizontal elbow is allowed for this configuration.
(for qualified installers only)
Exhaust Restrictor Position #4
Diffuser Open (stock)
Exhaust Restrictor Position #3
Diffuser Closed
Exhaust Restrictor Position #2
Diffuser Closed
Exhaust Restrictor Removed
Diffuser Closed
Horizontal Elbow
4121109
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
100-01329.docx