Advertisement

Enter a UPS Name and Description (optional) and identify if the UPS will be Connected Via USB
or over pre-configured serial port or via HTTP/HTTPS over the preconfigured network Host
connection.
Enter the UPS login details. This Username and Password is used by Slaves of this UPS (i.e.
other computers that are drawing power through this UPS) to connect to the Console Server for
monitoring of the UPS status and shutdown when battery power is low. Monitoring will
typically be performed using the upsmon client running on the Slave server. See section 8.5.4
for details on setting up upsmon on Slave servers powered by the UPS.
Note
: These login credentials are not related to the Users and access privileges you will have configured
in Serial & Networks: Users & Groups.
If you have multiple UPSs and require them to be shut down in a specific order, specify the
Shutdown Order for this UPS. This is a positive whole number, or -1. 0s are shut down first,
then 1s, 2s, etc. -1s are not shut down at all. Defaults to 0.
Select the Driver that will be used to communicate with the UPS. The drop-down menu
presents a full selection of drivers from the latest Network UPS Tools (NUT version 2.2.0) and
additional information on compatible UPS hardware can be found at:
http://www.networkupstools.org/compat/stable.html
Click New Options in Driver Options if you need to set driver-specific options for your selected
NUT driver and hardware combination (more details at:
http://www.networkupstools.org/doc