Horizontal Terminations using 6-5/8" Diameter Vent
Use a single 90°
elbow (NOTE:
an additional 45°
elbow may be
used on the
horizontal run).
The termination
must fall within
the shaded area
shown in the
chart. Use the
indicated
restrictor
position.
Travis Industries
10' (max)
5 feet
0 feet
NOTE:
• Horizontal sections require a 1/4" rise every 12" of travel.
• The maximum vertical length is 6'.
• The maximum horizontal length is 12'.
• Restrictor positions are based upon lab tests. The ideal restrictor position may vary slightly.
9 3 5 0 8 1 1 8
(for qualified installers only)
Use Restrictor
Position #1
Warning:
When an elbow is used directly off
the top of the fireplace, a 2"
clearance is required above the
vent (1" below and to the sides).
3 foot length (max)
2 7 0 9 0 0
10' (max)
5 feet
0 feet