Facility Characteristics; Floor Loading; Table C-3. Floor Loading Term Definitions - HP RP7405/7410 User Manual

Hp rp7405/7410 servers user guide
Table of Contents

Advertisement

Facility Characteristics

This section contains information about facility characteristics that must be considered for the installation or
operation of an hp rp7405/rp7410 server. Facility characteristics are:

Floor loading

Windows
Altitude effects
Floor Loading
The computer room floor must be able to support the total weight of the installed computer system as well as
the weight of the individual cabinets as they are moved into position.
Floor loading is usually not an issue in nonraised floor installations. The information presented in this section
is directed toward raised floor installations.
NOTE
Any floor system under consideration for an hp rp7405/rp7410 server installation should be
verified by an appropriate floor system consultant.
Raised Floor Loading
Raised floor loading is a function of the manufacturer's load specification and the positioning of the
equipment relative to the raised floor grid. While Hewlett-Packard cannot assume responsibility for
determining the suitability of a particular raised floor system, it does provide information and illustrations
for the customer or local agencies to determine installation requirements.
The following guidelines are recommended:
Because many raised floor systems do not have grid stringers between floor stands, the lateral support for
the floor stands depends on adjacent panels being in place. To avoid compromising this type of floor
system while gaining under floor access, remove only one floor panel at a time.
Larger floor grids (bigger panels) are generally rated for lighter loads.
Do not install any raised floor system until you have carefully examined it to verify that it is
CAUTION
adequate to support the appropriate installation.
Floor Loading Terms
Table C-3 defines floor loading terms.
Table C-3
Floor Loading Term Definitions
Term
Dead load
Live load
Appendix C
The weight of the raised panel floor system, including the
understructure. Expressed in lb/ft2 (kg/m2).
The load that the floor system can safely support. Expressed
in lb/ft2 (kg/m2).
Definition
Site Preparation
Facility Characteristics
117