At altitudes above 10,000 feet (3048 m), the lower air density reduces the cooling capability of air conditioning
systems. If your facility is located above this altitude, the recommended temperature ranges may need to be
modified. For each 1000 feet (305 m) increase in altitude above 10,000 feet (up to a maximum of 15,000 feet),
subtract 1.5 F (0.83 C) from the upper limit of the temperature range.

Air Conditioning System Guidelines

The following guidelines are recommended when designing an air conditioning system and selecting the
necessary equipment:
The air conditioning system that serves the computer room should be capable of operating 24 hours a day,
365 days a year. It should also be independent of other systems in the building.
Consider the long-term value of computer system availability, redundant air conditioning equipment or
capacity.
The system should be capable of handling any future computer system expansion.
Air conditioning equipment air filters should have a minimum rating of 45% (based on "AShRA Standard
52-76, Dust Spot Efficiency Test").
Introduce only enough outside air into the system to meet building code requirements (for human
occupancy) and to maintain a positive air pressure in the computer room.

Air Conditioning System Types

The following three air conditioning system types are listed in order of preference:
Complete self-contained package unit(s) with remote condenser(s)—These systems are available with up
or down discharge and are usually located in the computer room.
Chilled water package unit with remote chilled water plant—These systems are available with up or
down discharge and are usually located in the computer room.
Central station air handling units with remote refrigeration equipment—These systems are usually
located outside the computer room
Scalable overhead distribution system—This system distributes water overhead to air heat exchangers,
which cool the air locally over the servers. This system called DataCool
density environments of 100 to 500 watts per square foot.

Basic Air Distribution Systems

A basic air distribution system includes supply air and return air.
An air distribution system should be zoned to deliver an adequate amount of supply air to the cooling air
intake vents of the computer system equipment cabinets. Supply air temperature should be maintained
within the following parameters:
Ceiling supply system—From 55 F (12.8 C) to 60 F (15.6 C)
Floor supply system—At least 60 F (15.6 C)
If a ceiling plenum return air system or a ducted ceiling return air system is used, the return air grille(s) in
the ceiling should be located directly above the computer equipment cabinets.
The following three types of air distribution system are listed in order of recommendation:
Appendix C
Site Preparation
Environmental Elements
TM
is primarily used in high
111