Stabilization Parameter - Omron SYSDRIVE MX SERIES User Manual

Multi-function compact inverter
Table of Contents

Advertisement

Stabilization Parameter

•This function adjusts to reduce motor hunting.
•In case of motor hunting, check whether the motor capacity selection (H003/H203) and motor pole
number selection (H004/H204) match your motor. If they do not, match them.
•For adjustment, raise the stabilization parameter (H006) by degrees. If this increases motor
hunting, lower it by degrees.
•Other than this function, the following methods are suggested to reduce hunting:
•Lower the carrier frequency (b083)
•Lower the output voltage gain (A045)
Parameter No.
Function name
A045
Output voltage gain
b083
Carrier frequency
H006/H206
Stabilization parameter
FV/FI Adjustment
You can adjust the FV/FI frequency input.
Use this to change the full scale of input.
The set frequency becomes 0 Hz with 0.0% set.
This returns to the factory default value after initialization.
Function code
Item
C081
FV adjustment
C082
FI adjustment
Related functions
Data
20. to 100.
2.0 to 14.0
0. to 255.
Data
0.0 to 200.0%
0.0 to 200.0%
A011, A101, A012, A102, A013, A103, A014, A104, A015, A105
Maximum
frequency
Maximum
frequency
2
0 V/4 mA
5 V/12 mA
Description
Unit: %
If hunting occurs, reduce the set value.
Unit: kHz
If hunting occurs, reduce the set value.
If hunting occurs, adjust the set value.
Description
Unit: %
Unit: %
50.0%
100.0%
200.0%
10 V/20 mA
FV/FI input
4-2 Function Mode
4-34
4

Hide quick links:

Advertisement

Table of Contents
loading