Omron SYSDRIVE MX SERIES User Manual page 163

Multi-function compact inverter
Table of Contents

Advertisement

Query
No.
Field name
*
1
Slave address
2
Function code
3
Coil start number (MSB)
4
Coil start number (LSB)
5
Change data (MSB)
6
Change data (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
* There is no response for broadcasting.
Refer to "<Exception Response>" (page 4-74) if writing into the coil cannot be performed normally.
<Writing Into the Holding Register [06h]>
Writes data into the specified holding register.
(Example)
Write 50 Hz into the Inverter with slave address 5 as multi-step speed reference 0 (A020).
The data resolution of the holding register "003Ah" of multi-step speed reference 0 (A020) is 0.1 Hz.
To set 50 Hz, set the change data to "500 (1F4h)".
Query
No.
Field name
*
1
Slave address
2
Function code
Register start number
3
(MSB)
Register start number
4
(LSB)
5
Change data (MSB)
6
Change data (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
* There is no response for broadcasting.
Refer to "<Exception Response>" (page 4-74) if writing into the holding register cannot be
performed normally.
<Loopback Test [08h]>
Used to check the communications between master and slave. A random value can be used for test
data.
Response
Example
(HEX)
0 A
05
00
01
FF
00
DC
81
Response
Example
(HEX)
05
06
00
3 A
01
F4
A8
54
4-2 Function Mode
No.
Field name
1
Slave address
2
Function code
3
Coil start number (MSB)
4
Coil start number (LSB)
5
Change data (MSB)
6
Change data (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
No.
Field name
1
Slave address
2
Function code
Register start number
3
(MSB)
Register start number
4
(LSB)
5
Change data (MSB)
6
Change data (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
Example
(HEX)
0 A
05
00
01
FF
00
4
DC
81
Example
(HEX)
05
06
00
3 A
01
F4
A8
54
4-72