GB312 Applications Manual
5.5.2

Operating Conditions:

GB312 Venting System Table
Models
Input (MBH)
GB312-90
328
GB312-120
440
GB312-160
588
GB312-200
733
GB312-240
881
GB312-280
1029
GB312 Venting System Table
Models
Input (MBH)
GB312-90
328
GB312-120
440
GB312-160
588
GB312-200
733
GB312-240
881
GB312-280
1029
Note: Breeching pressure measured at outlet of
boiler vent connection.
Vent (Exhaust) Outlet Vertical
Vent
Venting
Total Equivalent
Connection
Diameter
Length of Vent (max)
at Boiler
(inches)
6"
6"
100
6"
6"
100
6"
6"
100
8"
8"
100
8"
8"
100
8"
8"
100
Combustion Air (inlet) Horizontal
Combustion
Combustion
Total Equivalent
Air Inlet
Air Pipe
Length of Combustion
Connection
Diameter
Air Pipe (max)
at Boiler
(inches)
4"
5"
100
4"
6"
100
4"
6"
100
4"
8"
100
4"
8"
100
4"
8"
100
Venting Parameters:
Vent Diameter for (minus
one) size diameter and
TEL in feet
5" = 100ft
5" = 80ft
5" = 50ft
7" = 100ft
7" = 100ft
7" = 100ft
Combustion Air Pipe
Diameter (minus one
inch) maximum TEL
in feet
4" = 40ft
5" = 75ft
5" = NA
7" = 100ft
7" = 100ft
7" = 100ft
7DEOH 
Vent Diameter for (minus
two) size diameter and
TEL in feet
4" = 55ft
4" = 30ft
4" = NA
6" = 70ft
6" = 55ft
6" = 35ft
Combustion Air Pipe
Diameter (minus two
inch) maximum TEL in
feet
3" = NA
4" = NA
4" = NA
6" = 45ft
6" = NA
6" = NA
_ 