Fit and seal the gas isolating valve supplied
to the boiler's gas connection.
1
2
3
Fig. 20 Gas valve pipe connection
1
Gas supply
2
Manual shut-off valve (supplied)
3
Sediment trap
4
Gas connection with isolating valve
4
7 747 010 720-22.1RS
Gas pipe delivery rate in cubic feet of
Length
gas per hour
of pipe
in feet
1"
1¼"
10
520
1060
20
350
730
30
285
590
40
245
500
50
215
440
75
175
360
100
160
305
150
120
250
Tab. 14 Gas pipe delivery rate
1) Maximum gas pipe delivery rate in cu ft/hr based on a gas spe-
cific gravity of 0.60 and a gas pressure of 0.5 psi or less and a
pressure drop equivalent to a water column of 0.3 inches.
Iron pipe
Equivalent lengths for pipe fittings
nominal
diameter (in
inches)
90°
elbow
Equivalent lengths in feet
1
3
4
5
2
7
8
Tab. 15 Equivalent lengths for pipe fittings
GB312 Applications Manual
1)
1½"
2"
2½"
1600
3050
4800
1100
2100
3300
890
1650
2700
760
1450
2300
670
1270
2000
545
1020
1650
480
870
1400
380
710
1130
in feet
Pipe fitting type
T-piece
Shutoff
Gas
valve
cock
5
0.6
1.60
6
0.8
2.15
7
1.0
2.50
10
1.3
3.00
12
1.6
3.50