Xii. Operation (continued)
C.
Controls Startup Check List
The Sage2.1 Control is factory programmed with default parameters. Before operating the boiler, these parameters must
be checked and adjusted as necessary to conform to the site requirements. Follow the steps below, making selections and
adjustments as necessary to ensure optimal boiler operation.
no.
Title
Terminal
Check Wiring
1
LWCO Plug
From the Home Screen press the Adjust button and login to access the adjust mode screens (if required, refer to "Entering Adjustment Mode"
Paragraph D, 4 for login instructions). The following parameters should be reviewed:
no.
Menu
Parameter
Air Sensor
Frost Protection
System
2
Setup
Warm Weather
Shutdown
Warm Weather
Shutdown Setpoint
Modulation
3
Boiler Type
Setup
System Pump
Pump
4
Boiler Pump
Setup
Domestic Pump
Contractor Name
Contractor
5
Setup
Manual
Manual Speed
6
Control
Central
7
Heat
Setback Setpoint
DHW
Setback Setpoint
8
Outdoor
Outdoor Reset
9
Enable/Disable
Reset
Modulation Source
Remote
10
4-20mA
Setpoint Source
Sequencer
Master Slave
11
98
Is the heating thermostat connected? Insure this is "dry", non-powered input.
1 & 2
Is an IWH providing a boiler heat demand?
2 & 3
Is an Outdoor Air sensor used? If yes, refer to step 2 and 9 to activate outdoor air reset.
5 & 6
Is a header sensor used? If yes, refer to step 11 below to activate this feature.
7 & 8
Is a Remote 4-20mA required for a building management system or external multiple boiler control?
9 & 10
If used see step 10 below to activate this input.
Is an External Limit used? Remember to remove factory-installed jumper.
11 & 12
Is a LWCO required? Check installation of the LWCO.
Outdoor
If an outdoor air temperature sensor is installed, press "Installed" otherwise leave as "Not Installed".
Selecting "Enable" will cause the boiler and boiler connected pumps to run for low temperature
events.
Selecting "Enable" will restrict boiler start during warm weather (only if an outdoor air temperature
sensor is installed).
Use this setting to adjust the temperature that the WWSD function will prevent a boiler start.
WaRning
Confirm that the correct boiler model is shown. Stop installation and contact factory if the wrong
boiler model is shown.
Ensure that the pump parameter selections are correct for your heating system. Refer to Section E.
Adjusting Parameters, Pump Setup Menu for additional information.
Enter your contact information, name, address, and phone number on this screen. In the event of
Address
a fault or the need to adjust a setting the display will direct the homeowner to you.
Phone
Use the "High and "Low" options to force the boiler to high fire and low fire for combustion testing.
Control
Ensure Setpoint, (firing rate target temperature) is correct for you type of radiation.
Setpoint
Check the setting for the central heat setpoint when the T-Stat "Sleep" or "Away" Setback mode is
entered (if EnviraCOM Setback thermostat is used).
Ensure Setpoint, (firing rate target temperature) is suitable for the IWH requirements.
Setpoint
Check the setting for the DHW setpoint when the T-Stat "Sleep" or "Away" Setback mode is entered
(if EnviraCOM Setback thermostat is used).
Select "Enable" to give domestic hot water demand priority over central heat demand.
Priority
Ensure the Outdoor Air Reset settings are correct for this site.
Set to 4-20mA when an external multiple boiler controller is connected to the system.
Set to 4-20mA when a Energy Management system is sending a "remote" setpoint.
Refer to Sequencer Master Setup Section X, G if multiple boilers are installed at this site.
Description
Description