Adjusting Parameters - Burnham ALPINE Installation, Operation And Service Instructions

Alpine series condensing high efficiency direct vent gas - fired hot water boiler
Hide thumbs Also See for ALPINE:
Table of Contents

Advertisement

X. Modular installation (continued)
G
. Modular Boiler Operating Information (continued)

4. Adjusting Parameters

From the "Home" screen select the Adjust button to access the adjust mode screens links (if required refer to "Entering
Adjustment Mode", Section XII, Paragraph D, 4 for login in instructions).
Sequencer
Master
"Press"
button to access the following parameters:
Factory
Range / Choices
Setting
Enable,
Disable
Disable
Boiler
Boiler Piped,
Piped
Primary Piped
Enable,
Disabled
Disable
Central Heat
195°F
Setpoint,
195°F
Sequencer
"Press"
button to access the following parameters:
Slave
Factory
Range / Choices
Setting
None
1-8
Use Boiler First,
Normal
Normal,
Use Boiler Last
3
1-5
Parameter and Description
Master Enable/Disable
The Sequencer Master Enable/Disable is used to "turn on" the Multiple Boiler Controller. Warning! enable
ONLY one Sequence Master.
indirect Water Heater (iWH)
Boiler Piped
Sequencer to respond to an Isolated DHW demand that is piped to a single boiler. The
individual boiler goes on "Leave" from the Sequencer Master and goes to DHW Service.
Primary Piped
The Sequence Master responds to the DHW Call For Heat. This allows one or more
boilers to provide heat to the IWH.
DHW Two Boiler Start
The Sequencer to immediately start two boilers for a DHW call for heat. Used when DHW is the largest
demand. Only visible when primary piped IWH is selected.
Stop all Boilers Setpoint
When this temperature is reached all boilers are stopped. This setpoint allows the Sequencer to respond to
rapid load changes.
Parameter and Description
Boiler address
Each boiler must be given a unique address. When "Normal" slave selection order is used, the boiler address
is used by the Master Sequencer as the boiler start order. The boiler address is also the Modbus Address
when a building automation system is connected.
Slave Selection Order
"Use Boiler First"; places the Slave in the lead.
"Normal"; firing order follows boiler number (1,2,3,..) order.
"Use Boiler Last"; places the slave last in the firing order.
Response Speed
This parameter adjusts the Sequence Master temperature controller Proportion Integral Derivative (PID)
values. A larger Response Speed value results in tighter, more active, PID control. This speed is used
whenever the Sequencer is released to modulate.