Gas Piping - Burnham ALPINE Installation, Operation And Service Instructions

Alpine series condensing high efficiency direct vent gas - fired hot water boiler
Hide thumbs Also See for ALPINE:
Table of Contents

Advertisement

Vii. gas Piping
WaRning
Failure to properly pipe gas supply to boiler may
result in improper operation and damage to the
boiler or structure. always assure gas piping is
absolutely leak free and of the proper size and
type for the connected load.
an additional gas pressure regulator may be
needed. Consult gas supplier.
WaRning
Size corrugated stainless steel tubing (CSST)
to ensure proper capacity and minimize flow
restrictions.
A.
Size gas piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to
boiler. Maximum allowable system pressure is ½
psig. Actual point of delivery pressure may be less;
contact gas supplier for additional information.
Minimum gas valve inlet pressure is stamped on
the rating label located in the boiler's vestibule
compartment.
Table 1a: Maximum Capacity of Schedule 0 Black Pipe in CFH* (natural gas) For gas Pressures
of 0.5 psig or Less
Nominal Pipe
Inside
Diameter, In.
Size, In.
½
0.622
¾
0.824
1
1.049
1.380
1.610
2
2.067
2.469
3
3.068
Nominal Pipe
Inside
Diameter, In.
Size, In.
½
0.622
¾
0.824
1
1.049
1.380
1.610
2
2.067
2.469
3
3.068
* 1 CFH of Natural Gas is approximately equal to 1 MBH; contact your gas supplier for the actual heating
value of your gas.
50
inlet Pressure 0.5 PSi or less; 0. inch W.C. Pressure Drop
10
20
30
131
90
72
273
188
151
514
353
284
1056
726
583
1582
1087
873
3046
2094
1681
4856
3337
2680
8584
5900
4738
inlet Pressure 0.5 PSi or less; 0.5 inch W.C. Pressure Drop
10
20
30
172
118
95
360
247
199
678
466
374
1392
957
768
2085
1433
1151
4016
2760
2217
6401
4400
3533
11316
7778
6246
2. Maximum gas demand. Refer to the boiler's input as
printed on its rating label. Also consider existing and
expected future gas utilization equipment (i.e. water
heater, cooking equipment).
3. Length of piping and number of fittings. Refer
to Tables 14A (natural gas) or 14B (LP gas) for
maximum capacity of Schedule 40 pipe. Table 15
lists equivalent pipe length for standard fittings.
4. Specific gravity of gas. Gas piping systems for gas
with a specific gravity of 0.60 or less can be sized
directly from Tables 14A or 14B, unless authority
having jurisdiction specifies a gravity factor be
applied. For specific gravity greater than 0.60,
apply gravity factor from Table 16. If exact specific
gravity is not shown choose next higher value.
For materials or conditions other than those listed
above, refer to National Fuel Gas Code, NFPA54/ANSI
Z223.1, or size system using standard engineering
methods acceptable to authority having jurisdiction.
B.
Connect boiler gas valve to gas supply system.
Length of Pipe, Ft.
40
50
60
62
55
50
129
114
104
243
215
195
499
442
400
747
662
600
1439
1275
1156
2294
2033
1842
4055
3594
3256
Length of Pipe, Ft.
40
50
60
81
72
65
170
151
137
320
284
257
657
583
528
985
873
791
1897
1681
1523
3024
2680
2428
5345
4738
4293
70
80
90
46
42
40
95
89
83
179
167
157
368
343
322
552
514
482
1063
989
928
1695
1576
1479
2996
2787
2615
70
80
90
60
56
52
126
117
110
237
220
207
486
452
424
728
677
635
1402
1304
1223
2234
2078
1950
3949
3674
3447
100
38
79
148
304
455
877
1397
2470
100
50
104
195
400
600
1156
1842
3256