V. STEP 5 -- SELECT AND INSTALL DUCTWORK
The design
and
installation
of the duct system
must
be in
accordance
with:
• the
standards
of the
NFPA
(National
Fire
Protection
Association)
for installation
of nonresidence
type air con
ditioning
and ventilating
systems;
• NFPA 90A or residence-type,
NFPA 90B; and/or
local codes
and residence-type,
NFPA 90B;
• and/or
local codes and ordinances.
Select
and
size
ductwork,
supply-air
registers
and
return
air grilles according
to ASHRAE
(American
Society of
Heating,
Refrigeration,
and Air Conditioning
Engineers)
rec-
ommendations.
Use the duct flanges
provided
on the supply
and return
air
openings
on the side of the unit. See Fig. 2 4 for connection
sizes and locations.
The
14tin. round
duct collars
(size 024-
048 units) are shipped
inside the unit attached
to the indoor
blower.
They
are field-installed
and
must
be removed
fl'om
the indoor
cavity prior" to start
up, even if they are not used
for" installation.
A. Install Flanges for Ductwork Connections (PAIZ060 Only)
The PA1Z060
units
are shipped
with flanges
which
must
be
field-installed
on the unit.
To install
unit flanges:
1. Five pieces of flange are shipped
on the return
air open
ing of the unit.
Remove
the flanges
from the shipping
position.
See Fig. 5. Screws
are field-supplied.
2. One piece of flange
is used as it is shipped
(straight).
Bend the other
4 pieces at right angles.
3. Install
the
straight
flange
on the
right
side
of the
return
air opening
in holes provided.
See Fig. 6. Flanges
should
stick
out from
unit
to allow for connection
of
ductwork.
4. Install
2 hand
formed
flanges
onto return
air opening
in holes provided
to form a rectangle
around
the return
air opening.
5. Install
remaining
2 hand-formed
flanges
around
dis-
charge
air opening
in holes provided.
6. Ductwork
can now be attached
to flanges.
When
designing
and
installing
ductwork,
consider
the
following:
• All units
should
have field-supplied
filters installed
in the
return-air
side of the unit.
Recommended
sizes
fox"filters
are shown
in Table
1.
• Avoid abrupt
duct size increases
and
reductions.
Abrupt
change
in duct size adversely
affects
air performance.
IMPORTANT:
Use flexible connectors
between
ductwork
and
unit
to prevent
transmission
of vibration.
Use suitable
gas-
kets to ensure
weathertight
and airtight
seal.
• Size ductwork
for cooling
air quantity
(cfln). The mini-
mum
air quantity
for proper
electric
heater
operation
is
listed in Table 2. Heater
limit switches
may trip at air quan-
tities
below those recommended.
HAND
FORM
STRAIGHT
PIECE
Fig. 6 -- Flanges
Installed
on PAIZ060
Units
/
/
/
FIVE PIECES
OF DUCT
FLANGE
ATTACHED
HERE
FOR
SHIPMENT
Fig. 5 -- Shipping
Location of Duct Flanges
(Size 060 Only)
Fig. 7 -- Area
Not to be Drilled
More than
3/4-in.
--6--