TROUBLESHOOTING
COOLING CHART
SYMPTOM
CAUSE
REMEDY
Compressor
and con-
Power failure
Call power company.
denser
fan will not
Fuse btown or circuit breaker tripped
Replace fuse or reset circuit breaker.
start.
Defective thermostat,
contactor, transformer,
Replace component.
or control retay
Insufficient line voltage
Determine cause and correct.
Incorrect or faulty wiring
Check wiring diagram and rewire correctly.
Thermostat
setting too high
Lower thermostat setting below room temperature.
Compressor
will not
Faulty wiring or loose connections
in
Check wiring and repair or replace.
start but condenser
compressor
circuit
fan runs.
Compressor
motor burned out, seized, or
Determine cause. Replace compressor.
internal overload open
Defective run/start capacitor, overload,
Determine cause and replace.
or start relay
One leg of 3-phase power dead
Replace fuse or reset circuit breaker.
Determine cause.
Compressor
cycles
Refrigerant overcharge
or undercharge
Recover refrigerant, evacuate system, and recharge
(other than normally
to capacities shown on nameplate.
satisfying
thermostat).
Defective compressor
Replace and determine cause.
Insufficient line voltage
Determine cause and correct.
Blocked condenser
Determine cause and correct.
Defective run/start capacitor, overload
Determine cause and replace.
or start relay
Defective thermostat
Replace thermostat.
Faulty condenser-fan
motor or capacitor
Replace.
Restriction in refrigerant system
Locate restriction and remove.
Compressor
operates
Dirty air filter
Replace filter.
continuously.
Unit undersized
for load
Decrease load or increase unit size.
Thermostat
set too low
Reset thermostat.
Low refrigerant charge
Locate leak, repair and recharge.
Leaking valves in compressor
Replace compressor.
Air in system
Recover refrigerant, evacuate system, and recharge.
Condenser
coil dirty or restricted
Clean coil or remove restriction.
Excessive
head
Dirty air filter
Replace filter.
pressure.
Dirty condenser coil
Clean coil.
Refrigerant overcharged
Recover excess refrigerant.
Air in system
Recover refrigerant, evacuate system, and recharge.
Condenser
air restricted or air short-cycling
Determine cause and correct.
Head pressure
too low.
Low refrigerant charge
Check for leaks, repair, and recharge.
Compressor
valves leaking
Replace compressor.
Restriction in liquid tube
Remove restriction.
Excessive
suction
High heat load
Check for source and eliminate.
pressure.
Compressor
valves leaking
Replace compressor.
Refrigerant overcharged
Recover excess refrigerant.
Suction
pressure
too
Dirty air filter
Replace filter.
low.
Low refrigerant charge
Check for leaks, repair, and recharge.
Metering device or Iow side restricted
Remove source of restriction.
Insufficient evaporator
airflow
Increase air quantity. Check filter -- replace if
necessary. Check for other evaporator
coil obstructions.
Temperature
too low in conditioned
area
Reset thermostat.
Outdoor ambient below 40 F
Install low-ambient
kit.
Field-installed
filter-drier
restricted
Replace.