Table 3 -- Electrical Data
NOMINAL
VOLTAGE
COMPRESSOR
OFM
UNIT
VOLTAGE
RANGE
PA1Z
(V-Ph-Hz)
Min
Max
RLA
LRA
FLA
FLA
Nominal kW*
--/--
024
208/230-1-60
187
254
10.9
61.0
0.9
2.4
3.8/ 5.0
7.5/10.0
--/--
3.8/ 5.0
030
208/230-1-60
187
254
15.2
69.4
1.5
2.4
7.5/10.0
11.3/15.0
--/--
3.8/ 5.0
208/230-1-60
187
254
15.9
86.0
1.5
2.8
7.5/10.0
11.3/15.0
036
15.0/20.0
--/--
3.8/ 5.0
208/230-3-60
187
254
8.9
64.5
1.5
2.8
7.5/10.0
11.3/15.0
15.0/20.0
--/--
3.8/ 5.0
208/230-1-60
187
254
18.5
97.6
1.5
2.8
7.5/10.0
11.3/15.0
042
15.0/20.0
--/--
3.8/ 5.0
208/230-3-60
187
254
10.9
73.0
1.5
2.8
7.5/10.0
11.3/15.0
15.0/20.0
--/--
3.8/ 5.0
208/230-1-60
187
254
21.3
107.0
1.5
4.2
7.5/10.0
11.3/15.0
048
15.0/20.0
--/--
3.8/ 5.0
208/230-3-60
187
254
12.3
73.0
1.5
4.2
7.5/10.0
11.3/15.0
15.0/20.0
5.0
230-1-60
207
254
26.9
128.0
1.4
6.2
10.0
15.0
20.0
--/--
3.8/ 5.0
060
208/230-3-60
187
254
17.7
128.0
1.4
6.2
7.5/10.0
11.3/15.0
15.0/20.0
5.0
460-3-60
414
508
9.0
63.0
0.7
3.2
10.0
15.0
20.0
IFM
ELECTRIC
HEAT
FLA
--/--
18.1/20.8
36.1/41.7
--/--
18.!/20.8
36.1/41.7
54.2/62.5
--/--
18.!/20.8
36.!/41.7
54.2/62.5
72.2/83.3
--/--
10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
--/--
18.!/20.8
36.1/41.7
54.2/62.5
72.2/83.3
--/--
10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
--/--
18.!/20.8
36.!/41.7
54.2/62.5
72.2/83.3
--/--
10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
20.8
41.7
62.5
83.3
--/--
10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
6.0
12.0
18.0
24.1
POWER SUPPLY
MCA
MOCP
16.9/ !6.9
20/ 20
25.6/ 29.0
30/ 30
48.1/
55.1
50/ 60
22.9/ 22.9
30/ 30
25.6/ 29.0
30/ 30
48.1/
55.1
50/ 60
70.7/ 81.1
80/ got
24.2/ 24.2
30/ 30
26.1/ 29.5
30/ 30
48.6/
55.6
50/ 60
71.2/ 81.6
80/ got
93.6/107.7
!00/110t
15.4/ !5.4
20/ 20
!6.5/
18.5
20/ 20
29.6/ 33.6
30/ 35
42.6/
48.6
45/ 50
55.6/ 63.6
60/ 70t
27.4/
27.4
35/ 35
27.4/ 29.5
35t 35
48.6/
55.6
50/ 60
71.2/ 81.6
80/ 90t
93.8/107.7
100/110t
17.9/ 17.9
25/ 25
17.9/ 18.5
25/ 25
29.6/ 33.6
30/ 35
42.6/
48.6
45/ 50
55.6/ 63.6
60/ 79t
32.3/ 32.3
40/ 40
32.3/ 32.3
40/ 40
50.4/ 57.3
60/ 60
72.9/ 83.4
80/ 90t
95.5/109.4
100/110t
21.1/ 21.1
25/ 25
21.1/ 2!.1
25/ 25
31.3/ 35.3
35/ 40
44.3/
50.4
45t 60
57.4/ 65.4
69/ 70t
41.2
50
41.2
50
59.8
60
85.9
90t
111.9
125t
29.7/
29.7
35/ 35
29.7/
29.7
35t 35
33.8/
37.8
35/ 40
46.8/
52.9
50/ 60
59.9/
67.9
60/ 70t
15.2
20
15.2
20
19.0
20
26.6
30
34.1
35
LEGEND
FLA
--
Full Load Amps
HACR
--
Heating, Air Conditioning
and Refrigeration
IFM
--
Indoor (Evaporator)
Fan Motor
LRA
--
Locked Rotor Amps
MCA
--
Minimum Circuit Amps
MOCP
--
Maximum Overcurrent
Protection
NEC
--
National Electrical Code
OFM
--
Outdoor (Condenser)
Fan Motor
DISCONNECT
SIZE
FLA
LRA
16/ !6
24/ 27
68
44/ 51
22/ 22
24/ 27
44/ 51
79
65/ 75
23/ 23
24/ 27
45/ 51
96
66/ 75
86/ 99
15/ !5
15/ 17
27/ 31
74
39/ 45
51/ 59
26/ 26
26/ 27
45/ 51
107
66/ 75
86/ 99
!7/
17
17/ 17
27/ 31
83
39/ 45
51/ 59
31/ 31
31/ 31
46/ 53
12!
67/ 77
88/101
21/ 21
21/ 21
29/ 32
87
41/ 46
53/ 60
40
40
55
14!
79
103
29/ 29
29/ 29
31/ 35
146
43/ 49
55/ 62
15
15
18
7!
24
3!
EXAMPLE:
Supply voltage is 460-3-60
A
B
¢
AB = 452 v
(_
BC = 464 v
AC = 455 v
Average voltage =
452 + 464 + 455
3
=
457
RLA
--
Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or
480 v. If power distribution voltage to unit varies from rated heater volt-
age, heater kW will vary accordingly.
tFuse or HACR circuit breaker.
NOTES:
1. In compliance
with NEC requirements
for multimotor and combina-
tion load and equipment
(refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR breaker.
2. Unbalanced
3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent-
age of voltage imbalance.
% Voltage Imbalance
= 100 x max voltage deviation from average voltage
average voltage
Determine
maximum deviation from average voltage:
(AB) 457 - 452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v
Maximum deviation is 7 v.
Determine
percentage of voltage imbalance:
7
% Voltage imbalance = 100 x --
457
= !.53%
This amount of phase imbalance
is satisfactory
as it is below the
maximum
allowable 2%.
IMPORTANT:
If the supply voltage phase imbalance is more than 2%
contact your local electric utility company
immediately.
--9--