RECEIVING AND INSTALLATION
I. STEP I--CHECK
EQUIPMENT
A. Identify
Unit
The unit
model number
and serial
number
are stamped
on
the unit
identification
plate.
Check
this information
against
shipping
papers.
B. Inspect Shipment
Inspect
fox" shipping
damage
while
unit is still oi1 shipping
pallet.
If unit appears
to be damaged
or is torn loose fi'om its
securing
points,
have it examined
by transportation
inspec
tars before removal.
Fox,yard
claim papers
directly
to trans
portation
company.
Manufacturer
is not responsible
for any
damage
incurred
in transit.
Check all items against
stripping
list. hmnediately
notify yotxr
local representative
if any item is missing.
To prevent
loss or dan]age,
leave all parts
in original
pack-
ages until installation.
II. STEP 2 -- PROVIDE UNIT SUPPORT
A. Slab Mount
Place
the unit on a rigid,
level surface,
suitable
to support
the unit
weight.
The flat surface
should
extend
approxi
mately
2 in. beyond
tire unit casing
on the 2 sides. The duct
connection
side and condensate
drain connection
sides should
be flush with the edge of the flat surface.
A concrete
pad or a
suitable
fiberglass
mounting
pad is recommended.
A 6 in. wide gravel
apron should
be used around
the flat sur-
face to prevent
airflow
blockage
by grass
or shrubs.
Do not
secure
the unit
to the flat surface
except where
required
by
local codes.
The unit should
be level to within
1/a inch. This is necessary
for the unit drain
to function
properly.
III. STEP
3 --
PROVIDE
CLEARANCES
The
required
minimum
service
clearances
and
clearances
to
combustibles
are
shown
in Fig.
2-4. Adequate
ventilation
and
condenser
air
must
be provided.
The
condenser
fan
pulls
air
through
the
condenser
coil
and
discharges
it through
tire
fan on the
top cover.
Be sure
that
the
fan discharge
does
not recirculate
to the
condenser
coil.
Do not
locate
the
unit
in either
a corner
or under
an
over-
head
obstruction.
The minimmn
clearance
under
a partial
over-
hang
(such
as a normal
house
overhang)
is 48 in. above
the
unit
top. The maximum
horizontal
extension
of a partial
over-
hang
must
not exceed
48 inches.
Do not
place
the
unit
where
water,
ice, or snow
from
an
overhang
or roof will
damage
or flood the
unit.
The
unit
may
be installed
on wood
flooring
or on Class
A, B, or C roof cov
ering
materials.
IV. STEP
4 --
PLACE
UNIT
Unit
can
be moved
with
tire
handholds
provided
in the
unit
basepan.
Refer
to Table
1 for operating
weights.
U:se extreme
caution
m prevent
(tamaqe
when
movJI\_
the unit.
Unit
mu_st
rolnaJi1
ill all u[)r_q]lt
posJHoi1
duriil_
_1]] nlovillg
oDer_lHolls.
The
unit
must
be level
for proper
condensate
drainage;
the
ground
level
pad must
be level
before
setting
the
unit
in place.
When
a field-fabricated
support
is used,
be sure
that
the
sup-
port
is level
and
that
it properly
supports
the
unit.
Table 1 -- Physical Data
UNIT PAIZ
024
030
036
042
048
060
OPERATING
WEIGHT (Ibs)
222
236
250
297
310
350
COMPRESSOR
TYPE
Reciprocating
REFRIGERANT
R-22
Charge (Ibs)
2.8
[
3.9
4.7
[
4.4
I
6.1
I
7.5
REFRIGERANT
METERING
DEVICE
Acutrol
TM
System
CONDENSER
COIL
"opper Tubes, Aluminum Plate Fins
Rows,,.Fins/in.
1...!7
1...!7
2...17
1...17
2...!7
2...17
Total Face Area (sq ft)
6.7
7.9
6.2
11.1
8.6
10.7
CONDENSER-FAN
MOTOR
Pro )elier
CFM
1600
2000
2000
2600
2600
2800
Nominal
Rpm
825
1!00
1100
1100
1!00
1100
Motor Hp
7_
¼
¼
¼
¼
Diameter (in.)
20
20
20
20
20
20
EVAPORATOR
COIL
_opper Tubes, Aluminum Plate Fins
Rows,,.Fins/in.
2...15
3...!5
3...15
3...15
3...!5
4...15
Total Face Area (sq ft)
2.8
2.8
3.1
3.9
4.3
4.9
EVAPORATOR-FAN
MOTOR
Direct Drive
Blower Motor Size (in.)
10 x 8
10 x 8
10 x 8
10 x 9
10 x 9
10 x 10
Nominal
Cfm
800
1000
!200
1400
1600
2000
Rpm Range
550-1000
550-1000
800-1050
800-1050
!000-1100
950-1100
Number
of Speeds
3
3
3
3
2
3*
Factory
Speed Setting
Low
Med
Low
Med
Low
Low
Motor Hp
¼
¼
½
%
1
CONNECTING
DUCT SIZES
Round
Square
Supply
Air (in.)
14
!3.9 x !3.9
Return Air (in.)
14
!3.9 x 27.8
FIELD-SUPPLIED
RETURN AIR FILTER1"
Throwaway
(in.)
24 x 24
24 x 24
24 x 24
24 x 24
24 x 30
24 x 30
"460-v motors are 2-speed only.
1-Required filter sizes shown are based on the ARI (Air Conditioning
and Refrigeration
Institute) rated airflow at a velocity
of 300 ft!min for throwaway
type or 450 ft/min for high capacity type. Recommended
filters are 1-in. thick,
--5--