Payne PA1R Series Installation, Start-Up And Service Instructions Manual
Payne PA1R Series Installation, Start-Up And Service Instructions Manual

Payne PA1R Series Installation, Start-Up And Service Instructions Manual

Single package rooftop electric heating / electric cooling units

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23
I. Step 1 - Provide Unit Support . . . . . . . . . . . . .
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . .
IV. Step 4 - Rig and Place Unit . . . . . . . . . . . . . . .
and Install Outdoor-Air Hood . . . . . . . . . . . . . . .
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24,25
I. Unit Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . 24
II. Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . 24
III. Compressor Mounting . . . . . . . . . . . . . . . . . . . . . 24
IV. Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
V. Refrigerant Service Ports . . . . . . . . . . . . . . . . . . 24
VI. Compressor Rotation . . . . . . . . . . . . . . . . . . . . . . 24
VII. Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
VIII. Safety Relief . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
IX. Ventilation (Continuous Fan) . . . . . . . . . . . . . . . 24
X. Operating Sequence . . . . . . . . . . . . . . . . . . . . . . 24
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-28
I. Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
II. Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
III. Condenser-Fan Adjustment . . . . . . . . . . . . . . . . 26
IV. Condenser Coil Grille . . . . . . . . . . . . . . . . . . . . . 27
V. Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . 27
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-31
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe pre-
cautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit. Electrical shock could cause personal injury.
1. The power supply (volts, hertz, and phase) must corre-
spond to that specified on unit rating plate.
installation, start-up and
service instructions
SINGLE PACKAGE ROOFTOP
ELECTRIC HEATING/ELECTRIC COOLING UNITS
Page
Cancels: New
2. The electrical supply provided by the utility must be suf-
ficient to handle load imposed by this unit.
1
3. Identify locations of electrical inlets, condensate drain,
duct connections and required clearances before setting
1
unit in place.
2
4. This installation must conform with local building codes
and with NEC (National Electrical Code) or NFPA
2
(National Fire Protection Association) 54 TIA-54-84-1.
2
Refer to Provincial and local plumbing or wastewater
7
codes and other applicable local codes.
5. Approved for outdoor installation on wood flooring or on
9
class A, B, or C roof covering materials.
Unit is shipped in the vertical configuration. To convert to
horizontal configuration, remove screws from side duct open-
ing covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation-side down.
Seals around duct openings must be tight. See Fig. 1.
NOTE: When installing any accessory item, see the man-
facturer's installation instructions packaged with the
accessory.
A qualified installer or agency must use only factory-authorized
kits or accessories when modifying this unit.
I. STEP 1 - PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. See Fig. 2. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to the unit. If electric or
control power is to be routed through the basepan, attach the
accessory thru-the-bottom service connections to the base-
pan in accordance with the accessory installation instruc-
tions. Connections must be installed before unit is set on roof
curb.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the
roof curb. Improperly applied gasket can also result in air
leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to func-
tion properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation Instructions for ad-
ditional information as required.
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of con-
denser coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
PA1R
Sizes 036-072
3 to 6 Tons
II PA1R-36-1

INSTALLATION

2/15/98

Advertisement

Table of Contents
loading

Summary of Contents for Payne PA1R Series

  • Page 1: Table Of Contents

    installation, start-up and PA1R service instructions Sizes 036-072 3 to 6 Tons SINGLE PACKAGE ROOFTOP ELECTRIC HEATING/ELECTRIC COOLING UNITS Cancels: New II PA1R-36-1 2/15/98 CONTENTS 2. The electrical supply provided by the utility must be suf- Page ficient to handle load imposed by this unit. SAFETY CONSIDERATIONS .
  • Page 2: Step 2 - Field Fabricate Ductwork

    When using the standard side drain connection, make sure II. STEP 2 — FIELD FABRICATE DUCTWORK the plug in the alternate bottom connection is tight before Secure all ducts to roof curb and building structure on verti- installing the unit. cal discharge units.
  • Page 3 CONNECTION SIZES ‘‘D’’ ALT UNIT SIZE CONNECTOR ‘‘B’’ ‘‘C’’ DRAIN POWER CONTROL PA1R ACY PKG HOLE CRBTMPWR001A00 ⁄ ⁄ (THRU-THE-BOTTOM) 1 -9 ⁄ 1 -4 ⁄ 036-072 [551] [406] [44.5] CRBTMPWR002A00 ⁄ ⁄ (THRU-THE-BOTTOM) ROOF CURB UNIT SIZE ‘‘A’’ ACCESSORY PA1R CRRFCURB001A00 1 -2 [356] 036-072...
  • Page 4 NOTE: Drain plug is shown in factory-installed position. Fig. 4 — Internal Trap Condensate Drain MAXIMUM ALLOWABLE DIFFERENCE (in.) Fig. 3 — Unit Leveling Tolerances NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended. Fig.
  • Page 5 ECONOMIZER CONNECTION SIZES CORNER CORNER CORNER CORNER STD UNIT WEIGHT WEIGHT WEIGHT WEIGHT WEIGHT UNIT ⁄ dia [28.6] field power supply hole WEIGHT PA1R Durablade ⁄ -14 NPT condensate drain ⁄ dia [35] power supply knockout 165.6 15.4 57.2 40.4 50.3 17.7 2 dia [50.8] power supply knockout...
  • Page 6 Table 1 — Physical Data BASE UNIT PA1R NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Durablade Economizer Roof Curb COMPRESSOR TYPE Reciprocating Reciprocating Reciprocating Scroll Quantity Oil (oz) REFRIGERANT TYPE R-22 Operating Charge (lb-oz) 4-11 5-13 7-11 CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins Rows...Fins/in.
  • Page 7: Step 5 - Make Electrical Connections

    A. Positioning CONTROL BOX LOW-VOLTAGE EVAPORATOR UNIT DISCONNECT ACCESS PANEL ACCESS PANEL FAN ACCESS Maintain clearance around and above unit to provide proper LOCATION PANEL (DISCONNECT airflow and service access. See Fig. 7. A properly positioned NOT SHOWN) unit will have the following clearances: ⁄...
  • Page 8 TO COMP FIELD POWER SUPPLY 208/230-3-60 DISCONNECT 460-3-60 208/230-1-60 PER NEC (SIZE 072 ONLY) COMP COMP FIELD POWER SUPPLY FIELD POWER SUPPLY DISCONNECT DISCONNECT 208/230-3-60 460-3-60 PER NEC PER NEC (SIZES 036-060) (SIZES 036-060) LEGEND — Contactor COMP — Compressor —...
  • Page 9: Step 6 - Make Outdoor-Air Adjustments And Install Outdoor-Air Hood

    VI. STEP 6 — MAKE OUTDOOR-AIR ADJUSTMENTS AND INSTALL OUTDOOR-AIR HOOD A. Manual Outdoor-Air Damper Assembly: 1. Determine quantity of ventilation required for building. Record amount for use in Step 8. 2. Remove and save outdoor-air opening panel and screws. See Fig.
  • Page 10 Table 2 — Electrical Data VOLTAGE COMPR DISCONNECT ELECTRIC HEAT* POWER SUPPLY RANGE (each) SIZE† UNIT NOMINAL PA1R V-PH-Hz TYPE Nominal MOCP** — — 25.3/25.3 35/35 24/24 97/97 3.3/ 4.4 15.9/18.3 25.3/26.4 35/35 24/24 97/97 4.9/ 6.5 23.8/27.3 32.8/37.4 35/40 30/34 97/97 6.5/ 8.7...
  • Page 11 Table 2 — Electrical Data (cont) VOLTAGE COMPR DISCONNECT ELECTRIC HEAT* POWER SUPPLY RANGE (each) SIZE† UNIT NOMINAL PA1R V-PH-Hz TYPE Nominal MOCP** — — 42.7/ 42.7 50/ 50 41/ 41 155/155 4.9/ 6.5 23.5/27.1 42.7/ 42.7 50/ 50 41/ 41 155/155 6.5/ 8.7 31.4/36.3...
  • Page 12 6. Remove and save 6 screws (3 on each side) from sides of B. Durablade Economizer the manual outdoor-air damper assembly. NOTE: Horizontal discharge block-off plate is shipped with 7. Align screw holes on hood with screw holes on side of the air hood package.
  • Page 13 7. Remove tape from outdoor-air thermostat (OAT). Fas- ten OAT to inside of hood using screws and speed clips ECONOMIZER provided. See Fig. 22. Make sure OAT terminals are CONTROL positioned up. BOARD 8. Replace outdoor-air opening panel using screws from Step 2.
  • Page 14 U-SHAPED ECONOMIZER HOLE CONTROL ECONOMIZER ECONOMIZER BOARD PLUG MOTOR SCREW (NOT SHOWN) WIRING HARNESS BAROMETRIC RELIEF DAMPER POSITION SETTING BRACKET Fig. 20 — Typical Durablade Economizer and Wiring Harness EXAMPLE: Given — Negative Pressure ....0.2 in. wg Outdoor Air .
  • Page 15: Step 7 - Adjust Evaporator-Fan Speed

    4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increas- ing fan speed increases load on motor. Do not exceed maxi- mum speed specified in Table 1. LEGEND OAT — Outdoor-Air Thermostat 5.
  • Page 16 Table 3 — Fan Rpm at Motor Pulley Settings* MOTOR PULLEY TURNS OPEN UNIT PA1R ⁄ ⁄ ⁄ ⁄ ⁄ 036† 1090 1055 1025 048† 1185 1150 1115 1080 1045 1015 060† 1300 1260 1220 1180 1140 1100 1060 1020 072** 1460 1420...
  • Page 17 Table 6 — Fan Performance, PA1R036 Vertical Discharge Units; Alternate Motor (Belt) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts Watts Watts Watts 1000 1039 1100 1013 1068 1200 1045 1090 1300 1047 1075 1122 1400 1032 1067 1110...
  • Page 18 Table 8 — Fan Performance, PA1R048 Vertical Discharge Units; Alternate Motor (Belt) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts Watts Watts Watts 1200 1008 1300 1029 1400 1052 1500 1001 1076 1600 1023 1100 1700 1005 1045 1124...
  • Page 19 Table 10 — Fan Performance, PA1R060 Vertical Discharge Units; Alternate Motor (Belt) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts 1500 685 1072 848 1153 1022 1221 1196 1256 1328 1280 1349 1320 1400 1600...
  • Page 20 Table 12 — Fan Performance, PA1R036 Horizontal Discharge Units; Standard Motor (Direct) LOW SPEED HIGH SPEED AIRFLOW 208 v 230, 460 v 208 v 230, 460 v (Cfm) Watts Watts Watts Watts 0.72 0.75 0.73 0.76 1000 0.67 0.69 0.70 0.71 1100 0.61...
  • Page 21 Table 14 — Fan Performance, PA1R048 Horizontal Discharge Units; Standard Motor (Direct) LOW SPEED HIGH SPEED AIRFLOW 208 v 230, 460 v 208 v 230, 460 v (Cfm) Watts Watts Watts Watts 1200 0.93 0.97 1.04 1.09 1300 0.86 0.90 0.96 1.02 1400...
  • Page 22 Table 16 — Fan Performance, PA1R060 Horizontal Discharge Units; Standard Motor (Direct) LOW SPEED MEDIUM SPEED HIGH SPEED AIRFLOW 208 v 230, 460 v 208 v 230, 460 v 208 v 230, 460 v (Cfm) Watts Watts Watts Watts Watts Watts 1500 1.01...
  • Page 23 Table 18 — Fan Performance, PA1R072 Horizontal Discharge Units; Standard Motor (Belt) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts 1800 1019 1099 1178 1031 1249...
  • Page 24: Start-Up

    START-UP To Shut Off Unit Set system selector switch at OFF position. Resetting ther- I. UNIT PREPARATION mostat at a position above room temperature shuts unit Make sure that unit has been installed in accordance with off temporarily until space temperature exceeds thermostat installation instructions and applicable codes.
  • Page 25: Service

    C. Cooling, Units without Economizer Two-Row Coils (size 072) (see Fig. 28) When thermostat calls for cooling, terminals G and Y1 are NOTE: Save all screws removed in this section. The screws energized. The indoor (evaporator) fan contactor (IFC), com- must be used when reinstalling the equipment.
  • Page 26: Condenser-Fan Adjustment

    III. CONDENSER-FAN ADJUSTMENT (Fig. 31) CONDENSER FAN 1. Shut off unit power supply. 2. Remove condenser-fan assembly (grille, motor, and fan). 3. Loosen fan hub setscrews. 4. Adjust fan height as shown in Fig. 31. 5. Tighten setscrews. 6. Replace condenser-fan assembly. A.
  • Page 27: Condenser Coil Grille

    IV. CONDENSER COIL GRILLE temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the Condenser coil grille is shipped factory-installed. No adjust- reading. Indoor-air cfm must be within the normal operating ments are required.
  • Page 28 Fig. 34 — Cooling Charging Chart; PA1R060 Fig. 35 — Cooling Charging Chart; PA1R072 (Scroll) —28—...
  • Page 29: Troubleshooting

    TROUBLESHOOTING Refer to Troubleshooting Tables 19-21 and Fig. 36 for additional information. Table 19 — Cooling Service Analysis PROBLEM CAUSE REMEDY Compressor and Power failure. Call power company. condenser fan will Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. not start.
  • Page 30 Table 20 — Durablade Economizer Troubleshooting PROBLEM CAUSE REMEDY Damper does not Indoor (evaporator) fan is off. 1. Check to ensure that 24 vac is present at terminal C1 on the IFC or that open. 24 vac is present at the IFO terminal. Check whether 24 vac is present at PL6-1 (red wire) and/or PL6-3 (black wire).
  • Page 31 LEGEND NOTES: 1. If any of the original wire furnished must be replaced, it must be — Adjustable Heat Anticipator Field Splice replaced with Type 90 C wire or its equivalent. — Contactor, Compressor 2. Three-phase motors are protected under primary single phasing —...
  • Page 34 Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG 1-800-962-9212 [ ] Packaged Service Training [ ] Classroom Service Training Copyright 1998 Payne Heating & Cooling, Indianapolis, IN CATALOG NO. 53PA-1R0...
  • Page 36: Start-Up Checklist

    REFRIGEANT DISCHARGE PSIG VERIFY REFRIGERANT CHARGE USING COOLING CHARGING CHARTS ON PAGES 27 AND 28. VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION (PA1R072 SCROLL ONLY) CL-1 Copyright 1998 Payne Heating & Cooling, Indianapolis, IN CATALOG NO. 53PA-1R0...

This manual is also suitable for:

Pa1r036Pa1r048Pa1r060Pa1r072

Table of Contents