Step 6 -- Provide For Condensate; Disposal; Step 7 -- Install Electrical - Payne PA1Z030 Installation, Start-Up And Service Instructions Manual

Pa1z packaged air conditioner
Table of Contents

Advertisement

• Insulate
and weatherproof
all external
ductwork.
Insulate
and cover with a vapor barrier
all ductwork
passing
through
conditioned
spaces. Follow latest
Sheet Metal and Air Con
ditioning
Contractors
National
Association
(SMACNA)
and
Air Conditioning
Contractors
Association
(ACCA)
mini-
mum installation
standards
for" residential
heating
and air
conditioning
systems.
• Secure
all ducts
to building
structure.
Flash,
weather-
proof, and vibration-isolate
duct openings
in wall or roof
according
to good construction
practices.
Figure
8 shows
a typical
duct
system
with
PA1Z
unit
installed,
INDOOR
THERMOSTAT
SOURCE_
POWER AND
LOW VOLTAGI
ENTRY
DISCONNECTS
COMPOSITE
PER NEC*
RUST-PROOF
UNIT AND
BASE PAN
_LECTRIC
CONDENSATE
HEATER)
DRAIN
CONNECTION
LEGEND
Power Wiring
--
Control Wiring
Condenser Airflow
_
Evaporator
Airflow
*Separate
disconnect
per
NEC
(National Electrical Code) required
for electric
heater when single-
point connection
is not used.
Fig. 8 -- Typical Installation
Table 2 -- Minimum Airflow for Safe Electric
Heater Operation
(Cfm)
024
030
UNIT SIZE PA1Z
I
I
036
042
048
060
700
875
1200
!225
1400
1750
B. Converting
Horizontal
Discharge
Units
to
Downflow
(Vertical)
Discharge
Condensate
water
can
be drained
directly
onto
the
roof
in
rooftop
installations
(where
permitted)
or onto
a gravel
apron
in
ground
level
installations.
Install
a field
supplied
con
densate
trap
at end of condensate
connection
to ensure
proper
drainage.
Make
sure
that
the
outlet
of the
trap
is at
least
1 in. lower
than
the
drain-pan
condensate
connection
to pre-
vent
the
pan
fl'om
overflowing.
See
Fig.
9A and
9B.
Prime
the
trap
with
water.
When
using
a gravel
apron,
make
sure
it slopes
away
from
the
unit.
If the installation
requires
draining
the condensate
water
away
fl'om
the
unit,
install
a 2 in. trap
using
a :_/4 in. OD tubing
or
pipe.
See
Fig.
9A and
9B.
Make
sure
that
the
outlet
of the
trap
is at least
1 in. lower
than
the
unit
drain-pan
conden-
sate
connection
to prevent
the
pan
from
overflowing.
Prime
the
trap
with
water.
Connect
a drain
tube
using
a minimum
of :_/4in. PVC,
3/4 in. CPVC,
or :_/4in. copper
pipe
(all field sup
plied).
Do not undersize
the
tube.
Pitch
the
drain
tube
down
ward
at a slope
of at least
1 in. for every
10 ft of horizontal
run.
Be sure
to check
the
drain
tube
for" leaks.
Prime
trap
at
the
beginning
of the
cooling
season
start-up.
Allowable
glues
fox" condensate
trap
connection
are:
Standard
ABS,
CPVC,
or
PVC
cement.
1" MIN.
t
TRAP
OUTLET I
2" MIN.
f
Fig. 9A --
Condensate
Trap
(Using
Tubing)
1" min.
%
TRAP
__OUTLET
&
I
Fig. 9B -- Condensate
Trap (Using PVC Piping)
VII. STEP 7 -- INSTALL ELECTRICAL
CONNECTIONS
Units
are dedicated
side supply
products.
They are not con
vertible
to vertical
air supply.
A field-supplied
plenum
must
be used to convert
to vertical
air discharge.
Vl. STEP 6 -- PROVIDE FOR CONDENSATE
DISPOSAL
NOTE:
Be sure that condensate
water disposal
methods
corn
ply with
local codes, restrictions,
and practices.
Unit removes
condensate
through
a lS/t;4-in. ID hole which is
located
at the end of the unit. See Fig. 2 4 for" location
of con
densate
connection.
--7--

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pa1z042Pa1z024Pa1z048Pa1z036Pa1z060

Table of Contents