Payne PA1Z030 Installation, Start-Up And Service Instructions Manual page 8

Pa1z packaged air conditioner
Table of Contents

Advertisement

Route thermostat wiresthrough grmnmet providing a drip
loopatthepanel. C onnect lowvoltage leads tothethermo
statasshown in Fig.13.
Theunittransformer supplies 2 4-vpower f orcomplete s ys-
temincluding accessory electrical heater. T ransformer is
facto W wiredfor230v operation. If supply voltage is 208 v,
rewire transformer primary asdescribed in theSpecial Pro
cedures for208-v O peration s ection b elow.
E. Accessory Electric
Heat Wiring
Refer to accessory
electric
heat
installation
instructions
for
information
on installing
accesso W electric
heat.
Accessory
electric
heat
wiring
is shown in Fig. 14.
F. Special Procedures for 208-V Operation
A. High-Voltage
Connections
The unit
must
have
a separate
electrical
service
with
a field
supplied,
waterproof
disconnect
switch
mounted
at, or within
sight
from
the
txnit.
Refer
to the
unit
rating
plate
fox" maxi-
mum
flxse/circuit
breaker
size
and
minimum
circuit
amps
(ampacity)
for wire
sizing.
See Table
3 fox" electrical
data.
The field supplied
disconnect
may
be mounted
on the unit
over
the
high
voltage
inlet
hole.
See Fig.
2 4.
B.
Routing
Power
Leads
into
Unit
Use only
copper
wire
between
disconnect
and
unit.
The
high-
voltage
leads
should
be in a conduit
until
they
enter
the
unit;
conduit
termination
at the
unit
must
be watertight.
Run
the
high
voltage
leads
through
the
hole
on the
control
box side
of
the
unit
(see Fig.
10 fox" location).
When
the
leads
are
inside
the
unit,
run
leads
to the
control
box
(Fig.
ll).
For
single-
phase
units,
connect
leads
to the
black
and
yellow
wires;
for
3-phase
units,
connect
the leads
to the
black,
yellow,
and
blue
wires
(see Fig.
12).
C. Connecting
Ground
Lead to Unit
Ground
Refer
to Fig.
11 and
12. Connect
the
ground
lead
to the
chas
sis using
the
unit
ground
lug in the
control
box.
D. Routing Control Power Wires
Form
a drip loop with
the thermostat
leads
before routing
them into the unit. Route the thermostat
leads through
grom
meted hole provided
in unit (see Fig. 10) into unit control box.
Connect thermostat
leads to unit control power leads as shown
in Fig. 13.
1. Remove wirenut
fl'om connection
of ORG wire to BLK
wire. Disconnect
the ORG transformer-primary
lead from
the BLK wire. Save wirenut.
See unit wiring
label.
2. Remove the wirenut
from tile terminal
on the end of the
RED transformer-primary
lead.
3. Save the wirenut.
4. Connect
the RED lead to the BLK wire from which
the
ORG lead was disconnected.
Insulate
with wirenut
from
Step I.
5. Using
the wirenut
removed
fl'om the RED lead,
insu
late the loose terminal
on the ORG lead.
6. Wrap the wirenuts
with electrical
tape so that the metal
terminals
cannot
be seen.
Indoor blower
motor speeds
may need to be changed
for 208 v
operation.
Refer to Indoor
Airflow
and Airflow Adjustments
section
on page I4.
HIGH-VOLTAGE
LOW-VOLTAGE
POWER
WIRING
WIRING
ENTRY
ENTRY
HOLE
HOLE
o
o
,
,9
:
,
o
=7==
..............
_,"
' 7.
/_
.................... X;:
=
Fig. 10 -- Unit Electrical Connection
Entry Holes
--8--