Nordyne M1B Installation Instructions Manual page 29

Downflow, direct vent (sealed combustion) forced air gas & oil furnaces
Table of Contents

Advertisement

Control Module
Status Indicators - M1M Series
Red LED Indicator
Status
Steady ON
Control OK
Steady OFF
No power
Rapid flash
False flame or internal control fault
One flash
Limit switch is open
Two flashes
Pressure switch is open
Three flashes
Pressure switch is stuck closed
Four flashes
Lockout due to failed ignition
Five flashes
L1 neutral reversed or L1 voltage not present on L1
Flame Status - A Yellow LED labeled "Flame" is provided to indicate flame status. When flame
is sensed, the flame LED is lit. If flame sense is weak, yellow LED will flash.
Control Module Status
Indicator - M1 B
Red LED Indicator
One flash
Status
The control is in lock-out because the inducer centrifugal
switch is or
was stuck closed.
The control is in lockout because the signal was not received by the
Two flashes
control that the inducer centrifugal
switch had closed within the time.
Three flashes
Fourflashes
The control is in lockout because a failed ignition attempt, a gas valve
error, or a false flame sensed during the warm up period. If false flame
has been sensed, the control will return to normal operation, and repeat
ignition sequence when the false flame is not present.
The control is in lockout due to a failure within the control board
Control
Module
Status
Indicator
- M5S Series
The LED indicator(s) on the oil primary control provides lockout, recycle and cad cell indications.
Honeywell
R7184 Control
Green LED Indicator
Status
On
Cad cell is sensing flame (could be flame or stray light)
Off
Cad cell is not sensing flame
Flashing - 1/2 sec. on, 1/2 sec. off
Lockout/Restricted Lockout
Flashing - 2 sec. on, 2 sec. off
Recycle
LED Indicator
Color
Red
Green
Yellow
Table 9. Control
Module
Status Indicators
Beckett
7505 Control
On Continuously
Restricted (hard) lockout
Cad cell is sensing flame -
(could be flame or stray light)
Pump prime mode or reset
button currently held for 15+ sec.
Flashing
Soft lockout
Recycle
N/A