Combustionair; Gas Gun; Oil Gun; Electrode Setting - Oil Gun - Nordyne M1B Installation Instructions Manual

Downflow, direct vent (sealed combustion) forced air gas & oil furnaces
Table of Contents

Advertisement

CombustionAir
Inorderforthe flameto burnefficiently, it must
receiveadequate combustion air.The amount
of combustion air required variesaccording to
altitude,actualB.T.U. c ontentof the fuel, gas
pressure, c onversion to another gasandother
factors. T he burnerflameshouldbe observed
andany necessary adjustments madebefore
the furnaceis placedintoservice. S eeTable7
for Factory Air settings.
CAUTION:
•,Combustion
air adjustment
must
be made only by a qualified
tech=
nician. Improper
air adjustment
may cause unsafe operation, ex=
plosion and/or fire asphyxiation.
,,if the input to the furnace
is too
great
because
of excessive
gas
pressure,
wrong
size nozzle or
orifice,
high
altitude,
etc.,
the
burner
flame
will be sooty and
can produce
carbon
monoxide,
which
could
result
in unsafe
operation,
explosion
and/or
fire
or asphyxiation.
Model
Nat. Gas
LP Gas
Oil
66,000
3.5
3.5
3.5
86,000
5.3
6
5
Table 7. Factory
Combustion
Air Settings
Gas Gun
Combustion
air box adjustment
is made to the
main burner by loosening the two lock nuts on
the plastic air shutter, located on the left side of
the burner blower housing. Air sh utter adjustment
line is located on the same side of the blower
housing. Turn the plastic shutter to a smaller
number (counter clockwise) for less air to a larger
number (clockwise) for more air. Gently tighten
the lock nuts after completing the adjustment. For
best results, use instrument to measure between
8 - 9% CO 2, after the combustion
air has been
adjusted. Note: Do not over-tighten the lock nuts.
This may damage the plastic air shutter.
The Smoke should be NO. 0 on the Bacharach
Scale, and 0 to 0.02 negative draft over fire.
Electrode
Setting
(Oil Gun Only)
Poor ignition of the oil spray may result if the
electrodes are not adjusted as shown in Figure
34. Do not permit any electrodes to be grounded
to any surface.
Switching
ignition
Control
between
interrupted
and intermittent
Duty
(Oil Gun
Only)
Honeywell and Beckett oil primary controls can
be switched between interrupted and intermittent
ignition control. To switch from interrupted
duty
(Factory set) to intermittent duty, remove the blue
wire from the quick-connect
terminal. Attach the
burner motor and igniter wire to the burner motor
(orange) control terminal by splicing or adding
tab adapters. Seal and isolate any bare wires.
GAP
I .._._
ELECTRODE
•,,='-==1 1/8"----._
]
b--
1
Figure 34. Oil Gun electrode
Position
Oil Gun Only
It is recommended that the CO 2and Smoke levels
be measured for maximum performance.
CO 2
readings should be 10 - 11% for 66,000 BTUH
furnaces and 12-13% for 86,000 BTUH furnaces.
23