Connecting Power Supply Wires; Low Voltage Wiring; Connecting Thermostat Wires; Verifying Anticipator Setting - Nordyne M1B Installation Instructions Manual

Downflow, direct vent (sealed combustion) forced air gas & oil furnaces
Table of Contents

Advertisement

Connecting
Power Supply Wires
1. Remove the furnace control panel cover.
2. Route wires (115 VAC) through
the strain
relief on the left side of the furnace control box
(see Figure 24).
3. Connect the hot wire to the black pigtail lead,
and the neutral wire to the white pigtail lead.
Secure all connections with suitable wire nuts.
4. Connect
the ground
wire to the grounding
screw.
5. Reinstall the control panel cover and secure
with the original mounting screws.
Low Voltage Wiring
The thermostat
must be installed
according
to the instructions
supplied
by the thermostat
manufacturer. Low voltage connections (24 VAC)
from the thermostat are wired to the terminal strip
on the integrated control in the furnace.
NOTE: The thermostat
must not be installed on
an outside wa!l or any other location where its
operation
may be adversely affected by radiant
heat from fireplaces, sunlight, or lighting fixtures,
and convective heat from warm air registers or
electrical
appliances.
The nominal
anticipator
setting is 0.4. (Refer to the thermostat
literature
for additional
information.)
Five-conductor thermostat wire is recommended
for 24 volt low-voltage circuit (2-wire is required
for furnace only; 5-wire for heating and optional
cooling systems). Refer to table 6 for thermostat
wire information.
Connecting Thermostat
Wires
1. Insert 24 volt wires through the plastic grommet
just above the control panel.
2. Connect the thermostat
wires to the furnace
low voltage pigtails (see Figure 25).
3. Connect
low-voltage
circuit
to the
wall
thermostat.
4.A hole may be made in the furnace cabinet
to ease thermostat
wiring. Make sure that the
wiring is protected from the sharp edge of the
added hole.
On-Off
Switch -__l
_
_,(_./Tbermostat
Wires
Furnace
Blower
-
q
i1_,_ / c°ntr°l
B°x
Plug
/,_e
'_ I _,dll
_
To combustion
Power"
If',
_I I Blower
or Flame
¢[_
Roll-out
Switch
Entry I!
_, _ _/_e'--- To Gas Valve
On-Auto
Switch
or Burner
(Heating
Models
Only)
Figure 24. Control
Panel (All IVlodels)
Verifying Anticipator
Setting
After the furnace is installed, check the thermostat
anticipator against the nominal setting of 0.4.
1. Connect the milliamp meter in series with one
of the gas valve's low voltage terminals.
2. Energize the gas valve.
3. Read the value of the milliamps.
4. Adjust the heat anticipator
of the thermostat
to the value on the milliamp meter. If the heat
anticipator
is set too high, the furnace may
delay turning on. If set too low, the furnace
may cycle frequently and not provide comfort
to the homeowner.
Thermostat
Wire Gauge
Recommended
T'STAT Wire
Length
(Unit to T'STAT)
2-Wire
5-Wire
(Heating)
(Heating/Cooling)
24
55
25
22
90
45
20
140
70
18
225
110
Table 6. Thermostat Wire Gauge
M1/IVl5 NC
Thermostat__
RC
Red
W
White
G
"- Green J_
Yellow
Ready Furnace
Red
o
White
®
Green
®
Grey
Y
--
==
Figure 25. Thermostat
Wiring
For
A/C Ready Models
Grounding
/K WARNING:
To minimize
personal
injury,
the
furnace
cabinet
must
have
an
uninterrupted
or
unbroken
electrical
ground.
The
controls
used
in this
furnace
require
an
earth ground
to operate
properly.
Acceptable
methods
include
electrical
wire or conduit
approved
for ground
service.
Do not use gas
piping as an electrical
ground!
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents