Troubleshooting; Standing Pilot Models; Direct Ignition Models - Nordyne M1B Installation Instructions Manual

Downflow, direct vent (sealed combustion) forced air gas & oil furnaces
Table of Contents

Advertisement

TROUBLESHOOTING
Standing
Pilot Models
Main Burner Does Not Ignite
1. Check the electrical supply to the furnace.
2. Verify the furnace furnace On-Off switch is in
the ON position.
3. Check for proper thermostat
operation.
4. Check for broken or open thermostat
wires.
5. Verify the insulation located on the inside of
the front panel is glued securely around the
fan switch and the limit switch.
6. Shut off the electrical supply to the furnace
and remove the electrical box cover.
7. Check for a defective transformer
or blown
fuse.
8. Check electrical circuit for proper grounding,
polarity,
and
make
sure
the
electrical
connections
are tight.
9. Check the limit switches. Did they fail to close?
10. Replace the electrical box cover and restore
electrical
power to the furnace.
Turn the
furnace On-Off switch to ON and raise the
thermostat setting above room temperature.
11. Check for 24 VAC at the gas valve. Replace
the valve if the pilot is established
and it
does not open when powered with 24 volts.
Powered (24 VAC) Gas Valve - No Main Flame
1. Verify the manual shut-off valve is OFF.
2. Check the pilot flame. It must be established.
3. Check the gas valve control lever. It must be
in the ON position.
4. Check incoming gas pressure.
5. Replace the gas valve if the main burner does
not come on under the above conditions.
Pilot Will Not Light or Goes Out
1. Check the incoming gas pressure.
2. Check
for the
proper
pilot
orifice.
See
specifications
on the furnace nameplate.
3. Check for proper pilot flame adjustment.
See
Burner Adjustment section (page 22).
4. Verifythe thermocouple
millivoltage. If reading
is not between
18 - 30 my., the gas valve
electromagnet
may be defective. Replace the
gas valve if necessary.
5. Verify the pilot shield is in place.
6. Check for gas leaks (page 18).
7. Check the flue assembly for air leaks.
8. See lighting procedures
(pages 20 - 22).
Main Flame Is Not Burning Properly
1. Check the manifold gas pressure.
2. Check for the correct main burner orifice. See
furnace nameplate for specifications.
3. Check the flue for any blockages
or loose
connections.
4. Check
the
combustion
air passages
for
blockage.
26
High Gas Bills
a. Verify the proper orifices are being used.
b. Check the return air system. Is it clear and
free of blockage?
c. Check the furnace filter. Is it clean or need
replacing?
d.Verify
the home is insulated,
windows
and
doors fit tightly, and there are no leaks in the
heating duct system.
e. Check the room thermostat.
Is the setting
higher than necessary? Low humidity requires
higher temperatures
for the same
level of
comfort. Check for proper humidity level in the
home.
Direct ignition
Furnaces including
Gas Gun
M1B Series (see Table 9, page 29)
Burner Motor won't Run - T-stat Calls for Heat
1. Check the electrical supply to the furnace.
2. Verify the furnace furnace On-Off switch is in
the ON position.
3. Defective thermostat
circuit - white and red
thermostat
low voltage
leads
(M1/M5M,
M1/M5B
models).
If the burner
motor
or
combustion fan runs, check:
. Thermostat
connections
. Thermostat
4. No voltage to control module - determine if 24
volts (or 120 volts) is available to the control
module. If voltage is not available check for:
. Blown fuse, defective transformer,
circuit
breaker, no electrical supply.
. Limit switch open.
. Loose connections.
Combustion
Blower Runs - No Flame
1. Defective centrifugal
switch (M1 B Model).
. Check the operation
of centrifugal
switch
by removing end bell of the burner motor.
. Clean contacts of motor.
. If the contacts are closed, replace the motor.
2. Defective pressure switch (M1 M & M1G - 077,
090 Models) - check air tube and electrical
connections.
3. Burner in purge mode - allow 75 seconds for
flame establishing
period.
4. Check for proper electrical
connections
at
purge timer, control box, or gas valve.
5. Check for gas supply- gas line valve on, control
lever on.
Control Module is Powered - Ignitor won't Heat
1. Disconnect ignitor leads atAMP receptacle and
check for 120 volts at the plug during ignition
sequence.
2. Replace
ignition
control if 120 volts is not
available at AMP plug during ignition sequence.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents