Oil Gun Models - Nordyne M1B Installation Instructions Manual

Downflow, direct vent (sealed combustion) forced air gas & oil furnaces
Table of Contents

Advertisement

120 VAC Is Available At AMP Plug_:___l nitor
Does Not Heat Up
1. Disconnect
power to the furnace.
2. Disconnect AMP plug to the ignitor, and check
ignitor resistance with an ohm meter. Set on
RX1 scale.
, Normal reading should be 40 - 75 ohms.
, If above or below this rating at room tem-
perature change ignitor.
3. Check for continuity from ignitor receptacle to
burner.
Main Flame Ignites - Burner Locks Out
, Ignition control is not properly grounded.
, Defective ignition control.
, Improper polarity of 120 volt power supply.
, Ignitor has hairline crack.
, Improper gas pressure or burner air adjustment
is not allowing flame to contact ignitor tip for
flame rectification.
, Misaligned
ignitor does not allow flame to
contact ignitor tip for flame rectification.
Burner Short Cycling - Thermostat
Calls for
Heat, Limit Switches Closed
, Check for polarity.
, Check ground.
, Check flue.
, Check combustion
air.
o Check gas pressure.
o Check orifice.
, Checkthe position of ignitor, a normal reading
should be 40-75 ohms.
24 Volts Supplied To Gas Valve During__lgl nition
- No Main Gas Flow
Gas valve
may be defective.
Replace
if
necessary.
, Gas
piping
may be plugged.
Check
for
adequate gas supply to gas valve at union.
Burner Operates - Insufficient Heat
, Check
thermostat
for proper
setting
and
location. Thermostat
should
not be located
where it will be affected by another heat source.
o Check for clean filter and proper air flow.
, Check burner for proper gas firing rate.
, Be sure unit is not undersized for its thermal
load.
, Check thermostat
anticipator.
The nominal
setting is 0.4.
Burner Flame Without Motor Running
Gas valve stuck open, check gas valve for
proper operation
(replace if necessary)
and
inspect heat exchanger.
o Check for 115 volts to the combustion blower
motor; replace if necessary.
, If no power to combustion
blower then check
wiring and control module; replace if necessary.
Circulation Air Blower Will Not Operate Even
Though The Burner Does Operate
, Check thermostat
G connection.
, Check wiring to motor.
, Check for a defective motor.
Oil Gun - Honeywell
R7184 or Beckett
7505
Controls Only - IVISS Series.
Burner does not start with a call for heat.
o Check the electrical supply to furnace.
, Verify the furnace door switch is in the ON
position.
, Check for line voltage (115 VAC) at the oil
primary control.
, Check indicator LED with burner off, no call
for heat (no flame). See Table 9 (page 29).
If green LED indicator is on, the cad cell is
seeing stray light or the cad cell of controller
is defective.
If green LED indicator is off, go immediately
to step 5.
If LED indicator is flashing (red or green on
Beckett 7505 control), refer to the next step
1 below - Reset primary control.
, Jumper T to T terminals on primary control.
If burner starts, check thermostat
or limit
wiring connections.
If burner does not start, turn off power. Check
all wiring connections.
If burner does not start, replace primary
control.
Burner
starts
and then
locks out on safety
with Honeywell
R7184 LED indicator flashing
1/2second on, 1/2second off. For Beckett 7505
control, the red LED will flash.
.
Reset primary control: To reset the control
from (soft) lockout, the button needs only to be
pressed and released. If the R7184 control is
in restricted mode, press and hold the button
for 45 seconds - until the LED flashes once. If
the 7505 control is in restricted mode, press
and hold the button in for 15 seconds until the
red turns off and the yellow LED turns on.
NOTE: Restricted
Lockout: If the control locks
out three times in a row without a complete heat
cycle between attempts, the lockout becomes a
restricted (hard) lockout.
2. If the LED indicator stops flashing
and the
ignition remains off, the primary control could
be defective. If line voltage is present at the
igniter
terminals,
and there
is no ignition,
the igniter is likely defective and needs to be
replaced.
3. If the stops flashing, burner turns on, but the
control locks out again, check the cad cell. If
27