Getting Started; Design And Installation Considerations; Negative Pressure - Heat & Glo LifeStyle RH-36 Series Owner's Manual

Woodburning
Table of Contents

Advertisement

2 2

Getting Started

A. Design and Installation Considerations
CAUTION
Check building codes prior to installation.
Installation MUST comply with local, regional,
state and national codes and regulations.
Consult insurance carrier, local building inspector,
fi re offi cials or authorities having jurisdiction about
restrictions, installation inspection and permits.
When planning a fi replace installation, it is necessary to de-
termine the following information before installing:
Where the fireplace is to be installed. See Sections
3 and 4.
The vent system confi guration to be used. See Sections
5 and 6.
Gas supply piping. See Section 7.
Framing and fi nishing details. See Sections 3, 6 and 8.
Draft is the pressure difference needed to vent fi replaces
successfully. Considerations for successful draft include:
Preventing negative pressure
Location of fi replace and chimney
Heat & Glo • RH-36/RH-42 • 4044-153 Rev S • 06/07
WARNING
Asphyxiation Risk
Negative pressure can cause spillage of
combustion fumes and soot. Fire needs to draft
properly for safe operation.
B. Negative Pressure
Negative pressure results from the imbalance of air avail-
able for the fi replace to operate properly. Causes for this
imbalance include:
Exhaust fans (kitchen, bath, etc.).
Range hoods.
Combustion air requirements for furnaces, water heaters
and other combustion appliances.
Clothes dryers.
Location of return-air vents to furnace or air
conditioning.
Imbalances of the HVAC air handling system.
Upper level air leaks: recessed lighting, attic hatch
opening, duct leaks.
To minimize the effects of negative air pressure, the follow-
ing must be considered:
Install the outside air kit. Install the intake on the side of
the house towards prevailing winds during the heating
season.
Ensure adequate outdoor air is supplied for combustion
appliances and exhaust equipment.
Ensure furnace and air conditioning return vents are not
located in the immediate vicinity of the fi replace.
Avoid installing the fi replace near doors, walkways or small
isolated spaces.
Recessed lighting should be a "sealed can" design; attic
hatches weather stripped or sealed; attic mounted duct
work and air handler joints and seams taped or sealed.
Basement installations should be avoided due to stack
effect. Stack effect creates negative pressure in lower
levels. Hearth & Home Technologies recommends the
use of direct vent fi replaces in basements.
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rh-42 series

Table of Contents