Install The Attic Insulation Shield - Heat & Glo LifeStyle RH-36 Series Owner's Manual

Woodburning
Table of Contents

Advertisement

E. Install the Attic Insulation Shield
WARNING
Fire Risk
DO NOT pack insulation or other
combustibles: between ceiling fi restops;
between chimney and attic insulation
shield.
ALWAYS maintain specifi ed clearances
around chimney and ceiling firestop
systems.
Install ceiling fi restops as specifi ed.
Failure to keep insulation or other material
away from chimney pipe may cause fi re.
An insulation shield must be installed when there is a pos-
sibility of insulation coming into contact with the factory built
chimney system. Installation of a ceiling fi restop is required
(see Figures 5.7 and 5.8).
Roll the shield (around the chimney if already installed)
until you have a 3 in. (76 mm) overlap and the three holes
on each side match up.
Insert three screws into the matching holes to form a
tube.
Bend three tabs on the bottom of the tube inward to 90°
to maintain chimney clearance. See Figure 5.6.
Tape over the resulting openings with aluminum tape to
prevent insulation being blown into them.
Rest the insulation shield on the ceiling fi restop below.
Bend the three short tabs at the top of the shield inward
to 90° to maintain the 2 in. (51 mm) clearance from the
chimney.
Bend the remaining top tabs to just meet the pipe.
Bend inward
90°
Figure 5.6
Prepare Attic Insulation Shield
20
Bend remaining tabs
to rest against pipe to
prevent insulation
from falling in.
Insert three
screws
3 in. (76 mm)
overlap
Heat & Glo • RH-36/RH-42 • 4044-153 Rev S • 06/07
Tape
here
Insulation
10-1/2 in.
(267 mm)
Figure 5.7
Install Attic Insulation Shield Above the Ceiling
6 Tabs bent
Insulation
10-1/2 in.
(267 mm)
Figure 5.8
Install Attic Insulation Shield Below the Ceiling
If you wish to make a custom shield or barrier, follow these
guidelines:
Metal is preferred, although any material stiff enough to
hold up against the insulation can be used.
The shield or barrier must be tall enough to extend above
the insulation and prevent blown-in insulation from spilling
into the cavity.
Maintain specifi ed cleaances around chimney.
Check instructions and local codes for further details.
Tabs bent in to
rest against pipe
Pipe
Attic Insulation Shield
14-1/2 in. (368 mm)
diameter
6 Tabs bent
in 90°
Ceiling Firestop
Pipe
Insulation
Tabs bent in to
rest against pipe
Pipe
Attic Insulation Shield
14-1/2 in. (368 mm)
diameter
in 90°
Tape
Insulation
here
Ceiling Firestop
Pipe

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rh-42 series

Table of Contents