13. ELECTRICAL CONNECTIONS - WALL TIMER VERSIONS

A. IDENTIFY ELECTRICAL REQUIREMENTS
The model number is printed on a plate at the pump end
of the module.
The model number identifies electrical rating. Electrical
connections for each model vary.
S K-1200-AC, K-1205-AC, K-1210-AC,
K-1215-AC, K-1220-AC:
See Electrical Requirements section on page 11 of
Product Requirements.
B. WIRING INFORMATION - 120 V, 60 HZ –

WALL TIMER VERSIONS

DANGER: Risk of electrical shock.
mount timer within reach of whirlpool user.
WARNING: Risk of electrical shock. To reduce
the risk of electric shock, connect only to a properly
grounded, grounding-type receptacle, protected
by a Ground-Fault Circuit-Interrupter (GFCI). Do
not remove the plug's grounding pin. Do not use a
grounding adapter.
Your Kohler Whirlpool bath is equipped with a cord and
plug. All wiring of the pump and control has been
completed at the factory. A licensed electrician must
install a GFCI protected, 120 Volt, 15 Amp, grounded
outlet. Your whirlpool may then be plugged into this
outlet. No other load should be on this circuit. Locate the
outlet within reach of the 36" cord.
Install wiring from the GFCI to the wall timer location.
Use a switch box with adequate capacity.
CA
106548-
(9437)
60 Hz
Do not
Black (Line)
White (Neutral)
G
F
C
I
Green (Ground)
20
TIMER
Black
Black
White
White
Green
Green
Kohler Co., Kohler WI
PUMP