3 I/O Specifications and Wiring for Pulse I/O Modules
3-2-2
I/O Circuit Configurations
Input Circuits (IN00 to IN05 and IN10 to IN15)
3.6 kΩ
24 V
LD+
0 V/LD−
Input Circuits (IN06 to IN09 and IN16 to IN19)
4.0 kΩ
24 V
LD+
0 V/LD−
Output Circuits (OUT00 to OUT05 and OUT10 to OUT15)
• Sinking-type I/O Module (CJ2M-MD211)
Isolation
circuit
3-2-3
Wiring
There are the following three methods for wiring a Pulse I/O Module.
• Using Connector-Terminal Block Conversion Units
Connector-Terminal Block Conversion Units are used when using normal I/O, quick-response
inputs, interrupt inputs, PWM outputs, or pulse outputs to stepping motors or other manufacturer's
Servo Drives.
• Using Servo Relay Units
Servo Relay Units are used when using OMRON's Servo Drives.
• Directly Connecting a Self-made Cable with a Connector
A self-made cable with a Connector can be used to directly connect the I/O.
3-8
100 Ω
100 Ω
100 Ω
100 Ω
Rated
+V
voltage
circuit
OUT
COM
• Sourcing-type I/O Module (CJ2M-MD212)
Isolation
circuit
Rated
voltage
circuit
CJ2M CPU Unit Pulse I/O Module User's Manual
COM
OUT
−V