Parameters - Baxi Bioflo Installation & Servicing Instructions Manual

Pellet central heating system boiler
Table of Contents

Advertisement

For the Service Technician

4.5.1 Parameters

The following parameters can be selected with the arrow buttons, then confirmed using the Choose button.
– Number of burner starts
– Fuel quantity auger conveyor
– Delivery time ignition phase
– Hysteresis Burner ON
– Maximum value of set temperature
– Set temperature ext. heating requirement
– Type of pellet feed system
– Operating time of suction turbine
– Profile ash removal
– Correction of cleaning interval
– Air intake/exhaust flap
– Limits for blower speed
– Install display module
– Language
– Installation
Number of burner starts
The number of burner starts of the FireWIN is displayed – Fig. 58.
Fuel quantity auger conveyor
The calculated fuel quantity (actual value) and the range is displayed in kg/h,
and can be adjusted – Fig. 59.
FireWIN
Actual
Factory setting:
value
Setting range:
Factory setting:
Range
Setting range:
Correc-
Factory setting:
tion
Setting range:
Delivery time ignition phase
Fuel quantity in the ignition phase – Fig. 60.
FireWIN
Factory setting:
Setting range:
Hysteresis Burner ON
Switching hysteresis for burner control – Fig. 61.
Factory setting:
Setting range:
0 – 20 K
FW 90
6.0 kg/h
±2 kg of range
6.0 kg/h
6.0 – 8.0 kg/h
0
±5
FW 90
120 s
100 – 150 s
5 K
FW 120
6.0 kg/h
±2 kg of range
6.0 kg/h
6.0 – 8.0 kg/h
0
±5
FW 120
100 s
80 – 130 s
40
Number of
burner starts
1.350
Fig. 58
Back
Fuel quantity
Auger conveyor
Actual value
6.0 kg
Range
6.0 kg
Correction
0
Choose
Back
Fig. 59
Delivery time
ignition phase
120
Save
Yes
No
Fig. 60
Hysteresis
Burner ON
5
Save
Fig. 61
Yes
No
s
+ +
K
+ +