For the Service Technician
4.5.1 Parameters
The following parameters can be selected with the arrow buttons, then confirmed using the Choose button.
– Number of burner starts
– Fuel quantity auger conveyor
– Delivery time ignition phase
– Hysteresis Burner ON
– Maximum value of set temperature
– Set temperature ext. heating requirement
– Type of pellet feed system
– Operating time of suction turbine
– Profile ash removal
– Correction of cleaning interval
– Air intake/exhaust flap
– Limits for blower speed
– Install display module
– Language
– Installation
Number of burner starts
The number of burner starts of the FireWIN is displayed – Fig. 58.
Fuel quantity auger conveyor
The calculated fuel quantity (actual value) and the range is displayed in kg/h,
and can be adjusted – Fig. 59.
FireWIN
Actual
Factory setting:
value
Setting range:
Factory setting:
Range
Setting range:
Correc-
Factory setting:
tion
Setting range:
Delivery time ignition phase
Fuel quantity in the ignition phase – Fig. 60.
FireWIN
Factory setting:
Setting range:
Hysteresis Burner ON
Switching hysteresis for burner control – Fig. 61.
Factory setting:
Setting range:
0 – 20 K
FW 90
6.0 kg/h
±2 kg of range
6.0 kg/h
6.0 – 8.0 kg/h
0
±5
FW 90
120 s
100 – 150 s
5 K
FW 120
6.0 kg/h
±2 kg of range
6.0 kg/h
6.0 – 8.0 kg/h
0
±5
FW 120
100 s
80 – 130 s
40
Number of
burner starts
1.350
Fig. 58
Back
Fuel quantity
Auger conveyor
Actual value
6.0 kg
Range
6.0 kg
Correction
0
Choose
Back
Fig. 59
Delivery time
ignition phase
120
Save
–
Yes
No
Fig. 60
Hysteresis
Burner ON
5
Save
Fig. 61
–
Yes
No
s
+ +
K
+ +