Setting The Boiler Parameters - Baxi HT 1.850 Installation, Operation And Maintenance Manual

Floor standing condensing gas boilers
Table of Contents

Advertisement

14. SETTING THE BOILER PARAMETERS

The boiler parameters may only be modi ed by professionally quali ed staff proceeding as follows:
a) press the
, keys on the boiler's front panel together for about 3 s until the parameter H90 appears on
the display;
b) press the
keys to select the parameter for modi cation;
c) press the
and
keys to modify the parameter;
d) press the
key to exit the programming function.
The following are the parameters generally used:
Parameter N.
Description
H90
Minimum D.H.W. temperature setting (°C).
D.H.W. activation program
H91
(0=active; 1=not active)
Maximum temperature (°C) of the central heating circuit HC1 corresponding to:
- the main circuit in systems with just one zone;
- the circuit of the zone where the QAA73 room temperature control device is installed in
H505
case of systems with more than one high-temperature zone;
- the high temperature zone circuit in mixed systems and if the SIEMENS AGU2.500
accessory is used.
Maximum temperature (°C) of the central heating circuit HC2 of a system with more than one
H507
zone, corresponding to the circuit of the low-temperature zone if the SIEMENS AGU2.500
accessory is used.
H516
Automatic Summer / Winter switching temperature (°C).
H532
Selection of temperature curve of central heating circuit HC1 (see Graph 1)
H533
Selection of temperature curve of central heating circuit HC2 (see Graph 1)
H608
PWM (%) Setting: Ignition load
H611
Speed setting (rpm) : Ignition load
H609
PWM Setting (%) : minimum power
H541-H610
PWM Setting (%) : maximum power Central heating / Domestic hot water
H612
Speed setting (rpm) : minimum power
H536-H613
Speed setting (rpm) : maximum power Central heating / Domestic hot water
H544
Pump post-circulation time in central heating mode (min)
H545
Burner operating pause time between two start-ups (s)
Hydraulic system setting (see instructions provided with the SIEMENS AGU2.500 accessory)
H552
H552 = 50 with AGU2.500 and with QAA73 + zones with room thermostat
H552 = 80 with RVA 47
Con guration of heating circuits
H553
H553 = 12 with AGU2.500
H615
Programmable function:
Con guration of system with supplementary pump
H632 = 00001111 with AGU2.500 and with QAA73 + zones with room thermostat
H632 = 00001111 with RVA 47
H632
The value of Bit could be 1 or 0.
Press the keys 5 and 6 to select the bit to modify (b0 is the bit on the right, b7 is the last bit on
the left).
To modify the Bit value press on the keys 7 and 8
H641
Fan overrun time setting (s)
Setpoint of autonomous ANTILEGIONELLA function
H657
60...80 °C = setting temperature range
0 = function inactive
If the electronic circuit board is replaced, make sure that the parameters set are those speci c to the boiler
model, as indicated in the documentation available from the authorised Service Centre.
ISTRUCTIONS PERTAINING TO THE INSTALLER
hydroheat.com.au
29
Factory setting
10
1
80
80
20
15
15
See
table 2
3
180
2
21
9
00001100
10
0
910.026.1 - EN (AUS)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ht 1.1000Ht 1.1200Ht 1.1500

Table of Contents