Venting - Vertical Terminations - Regency ULTRAGLOOW G36D-LP Owners & Installation Manual

Zero clearance direct vent gas fireplace
Table of Contents

Advertisement

INSTALLATION
RIDID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS
The G36D is approved for a maximum 23 ft. (7.0m) vertical, with a maximum 12 ft. (3.7m) horizontal offset
o
o
using two 90
elbows (two 45
Natural Gas, as per diagram 1.
The G36D is approved for a maximum 37 ft. (11.3m) straight vertical, including a maximum 20" (0.5m) horizontal
offset using two 90
o
elbow (two 45
and Natural Gas, as per the diagram 2.
Vent must be supported at offsets
Maintain clearances to combustibles as listed on pages 7 and 8.
Firestops are required at each fl oor level and whenever passing through a wall.
Note: Must use optional rigid pipe adaptor when using rigid pipe vent systems (Part # 510-994).
Note: UltraGlow Direct Vent System (Flex) is only approved for horizontal terminations.
16
(Propane & Natural Gas)
o
elbows equal one 90
elbow) with Rigid Pipe vent systems for Propane and
o
elbows equal one 90
o
elbow) with Rigid Pipe vent systems for Propane
Diagram 1
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace
Diagram 2