Clearances; Combustible Mantel Clearances; Mantel Leg Clearances - Regency P33-LP3 Owners & Installation Manual

Zero clearance direct vent gas fireplace
Table of Contents

Advertisement

CLEARANCES

The clearances listed below are Minimum dis-
tances unless otherwise stated:
A major cause of chimney related fi res is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this fi replace and
vent system be installed only in accordance
with these instructions.
Clearance to Combustibles from:
Back
0"
Side
0"
Floor
0"
NOTE: The minimum fl oor clearance must be
maintained from the top surface of the carpet-
ing, tile, etc.
Minimum Clearance from Top of Unit to:
Mantel*
min. 7" (177mm)
Ceiling
30"
from top of unit.
Side Wall Clearance
Bay or Flush Front
7-1/2" (191mm)
Minimum Vent Clearances:
2-1/2" (64mm) Horizontal Top
1-1/2" (38mm) Horizontal Side
1-1/2" (38mm) Horizontal Bottom
1-1/4" (32mm) Vertical Vent Clearance (Simpson)
1-1/2" (38mm) Vertical Vent Clearance (Flex)
Alcove Clearances:
Max. Depth
36"
Min. Width
48"
Min. Height
59"
* see mantel clearance instructions.
WARNING
Fire hazard is an extreme risk if these
clearances are not adhered to.
Clearances for Bay or Flush Front
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
Because of the extreme heat this fi replace emits, the mantel clearances are critical. Com-
bustible mantel clearances from top of unit are shown in the diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made
of metal studs covered with a non-combustible board.
(0mm)
(0mm)
(0mm)
(762mm)
(914mm)
(1219mm)
(1499mm)
This drawing is to scale at 1:6 (one inch = 6 inches). Mantel can be installed anywhere in shaded
area or higher using the above scale.
Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the
paint may discolour.
COMBUSTIBLE MANTELS

MANTEL LEG CLEARANCES

Combustible mantel leg clearances as per diagram below:
Maximum
1-1/2" projection at 2"
minimum clearance.
The HeatWave Duct Kit has different clear-
ance and framing requirements, check the
HeatWave manual for details.