Zero clearance direct vent gas fireplace (64 pages)
Summary of Contents for Regency PANORAMA P33E
Page 1
Panorama P33E Zero Clearance Owners & ® Installation Manual Direct Vent Gas Fireplace P33 Video www.regency-fire.com MODELS: P33E-NG10 Natural Gas P33E-LP10 Propane WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
Page 2
The P33E-10 has been approved by Warnock Hersey/Intertek for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace.
Page 3
This appliance is only use with the type of gas indicated on the rating plate. This appliance is #8 Mobile Home Ground not convertible for use with other gases, unless a certified kit is used. P33 Video Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Burner & Log Assembly ..........55 Gas Line Installation ..........32 Vignette Faceplate And Finishing Trim ....56 Pilot Adjustment ............33 Safety Screen And Louvers ........57 High Elevation ............33 Warranty ..............58 Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed. Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipm ent, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation. Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
UNIT DIMENSIONS WITH VIGNETTE AND VIGNETTE FINISHING TRIM UNIT DIMENSIONS WITH SAFETY SCREEN (#439-929) AND OPTIONAL LOUVERS Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Canadian Electrical Code. 3) See general construction and assembly in- Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Safety screen and Optional Louvers 10) Final check. Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to customer. 10 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
59" (1499mm) carpeting, tile, etc. clearances are not adhered to. * see mantel clearance instructions. MANTEL LEG CLEARANCES WITH VIGNETTE FACEPLATE Combustible mantel leg clearances from side of unit as per diagram: Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
MANTEL CLEARANCES WITH VIGNETTE + VIGNETTE ONLY (No Vignette Finishing Trim) VIGNETTE FINISHING TRIM STEPPED FINISH MANTEL CLEARANCES WITH MANTEL CLEARANCES WITH VIGNETTE + VIGNETTE FINISHING TRIM SAFETY SCREEN AND LOUVERS FLUSH FINISH 12 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
6" (15cm) with AstroCap termination cap or is 6" (15cm) with AstroCap termination cap or 12" (30cm) with Rigid Vent termination cap. (For 12" (30cm) with Rigid Vent termination cap. (For example Dura-Vent). Example Dura-Vent). Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Page 14
6) Use steel studs for framing where the 1-1/2" (38mm) clearance from the vent to combustible material cannot be maintained. The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details. 14 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
11. Using the two (2) screws provided secure the cover plate to the Receiver. Low Voltage Junction Box Profl ame Receiver J-Box Receiver Slider Switch Wall Plate 10 ft. wire harness with 12 pin connector Diagram 1 Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
There are 5 vent systems approved for use with the P33-10: the Regency Direct Vent Flex System for Horizontal Terminations only and the Simpson Dura- ®...
* Clearance in accordance with local installation codes and the requirements of the gas supplier 3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly 3 feet (91cm) above - if within 10 feet (3m) horizontally Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Termination Caps Figure 1 Wherever necessary due to external location of cap, the AstroCap can be replaced with the FPI Riser Vent Termination Cap or the Dura-Vent Snorkel Termination Cap. 18 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
2 x 4 or 2 x 6 walls. The liners must slip over the collars a minimum of 1-3/8". 6-7/8" Screws (175mm) (4 per connection) dia. air intake Wall Thimble 2 pieces (10" (254mm) Outer Diameter) Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
American Metal Products Ameri Vent Direct Vent, Security Secure Vent , Selkirk Direct-Temp. AstroCap is a proprietary trademark of FPI Fireplace ® Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc. 20 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
4DT-FS 4DFSP 4DFS SV4BF TM-4CS Trim Plate-Black 4DT-TP 4DFPB 4DcP SV4LA TM-4TP Regency Fireplace Products . 6988 Venture St. . Delta, BC . Canada . V4G 1H4 . 604-946-5155 . www.regency-fi re.com Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Page 22
Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard. Regency Fireplace Products . 6988 Venture St. . Delta, BC . Canada . V4G 1H4 . 604-946-5155 . www.regency-fi re.com 22 | Regency®...
Firestops are required at each floor level and whenever passing through a wall. • Maintain clearances to combustibles. Note: Must use optional rigid pipe adapter when using rigid vent systems (Part # 510-994). Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Page 24
Propane and Natural Gas. Maximum two 45 elbows allowed. • Vent must be supported at offsets. • Firestops are required at each floor level and whenever passing through a wall. • Maintain clearances to combustibles. 24 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Maintain clearances to combustibles. • Horizontal vent must be supported every 3 feet. • Firestops are required at each floor level and whenever passing through a wall. Minimum Minimum Flex Kit Center-Line Simpson Dura-Vent Center-Line Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Page 26
3' Max. 4' Min. 6' Max. Please note minimum 4' Max. 6' Min. 7' Max. 1 foot between 90 5' Max. 8' Min. 8' Max. elbows is required. 26 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Page 27
1 foot between 90 required. elbows is required. 5' Min. 8' Max. 6' Min. 6' Max. 6' Min. For additional vertical venting with 2 x 90 elbows, refer to "Rigid Pipe Venting Arrangements" Section. Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Page 28
5' Max. 7' Min. horizontal. 5' Min. 6' Max. 8' Min. Please note min. 1 foot 6' Min. 7' Max. 9' Min. between 90 elbows is required. 7' Min. 8' Max. 10' Min. 28 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Masonry chimneys may take various contours which Outer Pipe with Kit# 946-563 Air Intake Pipe Length Co-Linear Flex Rigid Pipe Adapter Adapter # 510-994 with Kit# 946-563 45 Elbow Inner Pipe Adapter with Kit# 946-563 Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
VENTING ARRANGEMENTS - VERTICAL TERMINATIONS with Co-linear Flex System for both Residential & Manufactured Homes into Masonry Fireplaces Horizontal Distance (Feet) The shaded area in the diagrams show the allowable vertical terminations. 30 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
“Mill- pipe. clearances. Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
885 S.I.T. VALVE DESCRIPTION 1) 6 Stage flame adjustment 2) Pilot adjustment 3) Inlet Pressure Tap 4) Outlet Pressure Tap 5) Pilot Outlet 6) Main Gas Outlet 7) Main Gas Inlet Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Remove burner orifice with a 1/2" wrench and discard. Use another wrench to hold on to the elbow behind Remove the 2 screws holding the Burner the orifice. Assembly to the firebox base. Push the Installer Notice: Burner Assembly to the left and lift out. These instructions must be left with the appliance. 34 | Remove the 2 screws, push Burner Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace Assembly to the left and lift out.
5) Slide the Top Brick Panel into position and slide the Top Brick Retaining clips so that they hold the Top Brick Panel in place and tighten down the screws. 2nd Grate Tab Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Vignette frame (see below). Screen below. assembly is secured at bottom with magnets. Screen Assembly Vignette Frame Reverse Steps to remove. Secure Vignette frame using 2 screws in locations shown below. Final Install Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Hook Vignette Faceplate brackets into place. Line up the screw holes on the fi nishing trim and Vignette Face- plate bracket with the unit–fasten with one screw on each side– P33 only. 05.04.15 919-566 38 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Inlay through the actual screen. NOTE: Ensure Inlay is in correct position before pushing studs through the safety screen. Stud Nut + washer (supplied) Completed Install Line up Inlay–Push studs on Inlay through screen Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace 05.21.15 919-559...
Line up the screw holes on the finishing trim and Vignette Faceplate bracket with the unit–fasten with one screw on each side. Reinstall the glass door and safety screen. Finishing Trim Top Finishing Trim Side 40 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace 10.29.14 919-475...
Loosen the screws–slide deflector on and tighten screws. allow access to attach bottom louver brackets to unit with one screw on each side in locations shown below. Magnet locations 07.21.15 919-558a Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Caution: Ensure that the wires do not touch any CAUTION: Label all wires prior to disconnection hot surfaces and are away from sharp edges. when servicing controls. Wiring errors can cause improper and dangerous operation. 1 of 10 42 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
When complete turn remote receiver to the ON position. Unit will now operate using the wall thermostat. NOTE: When the remote receiver is set to ON position, the remote control transmitter and all of its features are now dis- abled. Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
THESE FANS COLLECT A LOT OF DUST FROM WITHIN YOUR HOME. ENSURE YOU MAINTAIN THESE FAN MOTORS ON A REGULAR BASIS BY VACUUMING THE FAN BLADES AND THE HOUSING WITH A SOFT BRUSH NOZZLE. 44 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
2. Tuck any loose wires neatly underneath the firebox–inside the fireplace. Note: Ensure that wires do not touch the underside of the fire box (Keep wires away from heat as much as possible). AC adaptor Wire adaptor Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace 10/09/14 919-063...
Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. 46 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
2. Press and release the ON/OFF button on the remote handheld transmit- to the unit. ter (see Diagram 2). An audible beep should be heard from the receiver. ON/OFF Button Diagram 2 Remote shown in Manual Mode on Hi Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Utiliser l'interrupteur mural ou la télécommande pour mettre le système sur ON/OFF. Appuyer sur la touche ''OFF'' de la télécommande. Mettre le bouton de commande de gaz sur ''OFF'' pour éteindre la veilleuse. DO NOT REMOVE THIS INSTRUCTION PLATE 919-401 48 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
The glass should be cleaned or the film will bake on and become very difficult to remove. Use a non-abrasive cleaner and NEVER clean the glass while it is hot. Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
"cracking" and "ticking" sounds will be severely alter the unit's performance heard throughout the cycling process. which is not covered under warranty. GLASS GASKET 50 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
WARNING: Do not operate the appli- ance with the glass panels removed, cracked or broken. Replacement of Flush Glass Replacement Remove the flush door front. Remove the 4 glass clips from each corner. Slide in the new Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
6) Disconnect the Electronic modulator, EV1, EV2, and ground wires from the valve - as shown below. INSTALLING VALVE Ground 1) Install new valve assembly. 2) Reverse steps 9 through 1. Electronic Modulator 52 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Brick Panel - Rear 510-994 Rigid Pipe Adaptor Brick Panel - Left Side 919-394 Manual Brick Panel - Right Side Brick Panel - Top *Not available as a replacement part. 430-056 Brick Clip - Top Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Remote transmitter (GTMF) 910-127 Battery compartment door 911-037 Flame sense 911-038 Flame electrode 911-039 Pilot hood 911-432 Pilot tubing 911-137 Pilot clip 911-030 Fan control module *Not available as a replacement part. Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Vignette Door Inlay Black Chrome 439-924 Vignette Faceplate Black 439-949 Vignette Door Inlay Mt. Black 439-926 Vignette Faceplate Tuscan Sunset 439-950 Vignette Door Inlay Tuscan Sunset Parts Not Shown 430-940 3 sided Finishing Trim 56 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
SAFETY SCREEN AND LOUVERS Part # Description 430-922 Flush louvers black 439-929 Safety Screen Regency Logo Plate 948-216 ® Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
The purchase price must be confirmed by the original Bill of Sale. 58 | Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Page 59
Minor movement, expansion and contraction of the steel is normal and is not covered under the terms of this warranty. Freight damages for products or parts are not covered under the terms of the warranty. Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace...
Page 60
Product Registration and Customer Support: Thank you for choosing a Regency Fireplace. Regency strives to be a world leader in the design, manufacture, and marketing of hearth products. To provide the best support for your product, we request that you complete a product registration form at http://www.regency-fire.com/Customer-Care/Warranty-Registration.aspx...
Page 61
Product Registration and Customer Support: Thank you for choosing a Regency Fireplace. Regency strives to be a world leader in the design, manufacture, and marketing of hearth products. To provide the best support for your product, we request that you complete a product registration form found on our Web Site under Customer Care within ninety (90) days of purchase.