Quadra-Fire 31M-ACC-GT Owner's Manual page 13

3100 wood stove series, advanced combustion control (acc)
Table of Contents

Advertisement

R
For the Step Top Pedestal Model In US installations, it is
necessary to install a fl oor protector of a minimum of 3/8 inch
(9.5mm) thick metal clad millboard or equivalent a minimum of
16 inches (406mm) in front of glass and 8 inches (203mm)
to both sides of the fuel loading door. Open the door and
measure 8 inches (203mm) from the side edge of the open-
ing in the face of the appliance. *See page 12 for Canadian
clearances and horizontal venting exception.
Fuel loading door
16 in. from glass
31-5/8 in.
minimum
Figure 13.1
203mm (8 in.)
203mm
(8 in.)
457mm (18 in.)
1041mm (41 in.)
minimum
Figure 13.2
NOTE: •
March 2, 2007
Step-Top Uni-Body Model
3-1/4 in.
4-3/4 in.
39-5/8 in.
minimum
8 in.
USA
203mm
(8 in.)
1254mm
(49-3/8 in.)
minimum
CANADA
Illustrations and photos refl ect typical installations and are FOR DESIGN PURPOSES ONLY.
Illustrations/diagrams are not drawn to scale.
Actual installation may vary due to individual design preference
Hearth & Home Technologies reserves the right to alter its products.
For the Step Top Leg Model In US installations, it is nec-
essary to install a fl oor protector of a minimum thickness of
1-1/4 inch (32mm) or 1/2 inch of "k" value of 0.84 thick metal
clad millboard or equivalent a minimum of 16 inches (406mm)
in front of glass and 8 inches (203mm) to both sides of the
fuel loading door. Open the door and measure 8 inches
(203mm) from the side edge of the opening in the face of
the appliance. *See page 12 for Canadian clearances and
horizontal venting exception.
27-5/8 in.
Figure 13.3
Must extend 2 in. (51mm) beyond
each side of pipe (shaded area)
Figure 13.4
7033-277C
3100 Wood Stove Series (ACC)
USA required
Canada recommended
27-5/8 in.
USA
Page 13