Side Vent, Wall Mounted Termination Graph H*42Df-St; Side Vent, Wall Mounted Termination (Two Elbows) - Montigo H42DF ST Installation & Maintenance Manual

Indoor residential gas fireplace
Table of Contents

Advertisement

Notes Wall Mounted Terminations: SIDE VENT
SIDE VENTED INSTALLATIONS MUST BE MULTI ELBOW
SIDE VENTED INSTALLATIONS MAY NOT TERMINATE
STRAIGHT THROUGH THE WALL.
All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting graphs,
see Figure 12.
Fireplace must be converted to Side Vent configuration prior to
running vent, see Figure 7 and 7a.
The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of the
termination and the horizontal run from the fireplace flue collar to the wall
flange of the termination. Plot on the Venting Graph Figure 12 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall flange of the vent termination is 138", this would be
an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 48" and the horizontal
run to the wall flange of the vent termination is 96", this would be
this would NOT be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72" and
the horizontal run to the wall flange of the vent termination is 120",
this would NOT be an acceptable installation.
WARNING:
An inspection of the explosion relief flappers and door
MUST be made prior to lighting the fireplace. A faulty seal
on the door gasket and/or explosion ports will result in
products of combustion leaking into the living space and
may result in carbon monoxide poisoning.
XG0237 - 120611.1
Installation
Acceptable vent run
within non-shaded area.
Figure 12. Side Vent Venting Graph for wall mounted terminations.
Figure 12a Side Vented, wall mounted Multi-elbow termination installation.
The vent run must comply with the Venting Graph for Side vent, wall mounted
terminations, Figure 12.
H*42DF ST Indoor Gas Fireplace
A
C
Unacceptable vent run
within shaded area.
B
52"
42"
If your isnstallation does not fall
within the venting parameters,
please contact local Montigo dealer
for Power Venting options.
30" Max.
Flex or Rigid
Section
14 1/2"
Min.
12"
Max.
37"
Hearth
52" Min
Page 13