Side Venting Layout: Wall mounted
termination. L38ST:
Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the fireplace flue collar
to the wall flange of the termination. Plot on the Venting Graph Figure
15 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall flange of the vent termination is 138", this would be an
acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 48" and the horizontal run
to the wall flange of the vent termination is 96", this would be would
not be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72" and the
horizontal run to the wall flange of the vent termination is 120", this
would not be an acceptable installation.
Notes Wall Mounted Terminations: Side Vent
• All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
• Vent runs must fall within the limits set by the venting graphs, see
Figure 15.
• Fireplace must be converted to Rear Vent configuration prior to
running vent, see Figure 9 and 9a.
132
120
Acceptable vent run
within non-shaded area.
108
96
84
72
60
48
42''
36
26¾''
24
42''
12
12''
0
0
12
24
36
48
60
Horizontal Run (In.)
Figure 8.b Side Vent Venting Graph for wall mounted terminations.
16
A
C
B
Unacceptable vent run
within shaded area.
72
84
96
108
120
132
144
156
168 180
Flex or Rigid
Hearth
Figure 9.c Side Vented, wall mounted Multi-elbow termination installation. Installation for
L38DF*-ST must have a minimum vertical rise of 42".The vent run must comply with the Venting
Graph for Rear vent, wall mounted terminations, Figure 13.
12'' Max. horizontal
run with no vertical lift
Hearth
Figure 9.c Straight run, Side Vented, wall mounted termination for L38DF-ST*, Figure 13.
Installation
30''
Max.
15¼''
Min.
42''
Min.
26¾''
12''
Max.
PXT Extension
Heat Shield
Termination
26¾''
12''
Max
Max.