Notes Wall Mounted Terminations: SIDE VENT
All dimension lengths for vertical or horizontal runs are measured
from centre of the vent pipe.
Venting runs must fall within the limits set by the venting graphs,
see Figure 14.
Fireplace must be converted to Side Vent configuration prior to
running vent, see Figure 9 and 9a.
The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of the
termination and the horizontal run from the fireplace flue collar to the wall
flange of the termination. Plot on the Venting Graph Figure 14 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall flange of the vent termination is 138", this would be
an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 48" and the horizontal
run to the wall flange of the vent termination is 96", this would
NOT be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72" and
the horizontal run to the wall flange of the vent termination is 120",
this would NOT be an acceptable installation.
132
Acceptable vent run
120
within non-shaded area.
B
48"
42"
33 1/2"
12"
Figure 14. Side Vent Venting Graph for wall mounted terminations.
XG0207 - 011012.1
Installation
A
A
C
C
Unacceptable vent run
within shaded area.
If your installation does not fall within
the venting graph parameters,
please contact a local Montigo dealer
for Power Venting Options.
NOTE:
12" MAX. horizontal
run with no vertical lift.
Hearth
Figure 14a. Straight run, Side Vented, wall mounted termination for H*38DF*-
ST, Figure 14.
Flex or Rigid
Section
Figure 14b. Side Vented, wall mounted Multi-elbow termination installation.
Installation for H*38DF*-ST must have a minimum vertical rise of 48". The
vent run must comply with the Venting Graph for Side vent, wall mounted
terminations, Figure 14.
WARNING:
An inspection of the explosion relief flappers and door
MUST be made prior to lighting the fireplace. A faulty seal
on the door gasket and/or explosion ports will result in
products of combustion leaking into the living space and
may result in carbon monoxide poisoning.
H*38DF ST Indoor Gas Fireplace
PXT Extension
RHS101 Heat
Shield
Termination
12" MAX.
33 1/2"
Exterior
Wall
30" Max.
14 1/2"
Min.
48" Min
12"
Max.
33 1/2"
Hearth
Page 13