Combustible Mantel; Clearances; Gas Connection; Venting - Regency Sunrise U32SE-NG5 Owners & Installation Manual

U32se sunrise gas insert
Table of Contents

Advertisement

COMBUSTIBLE MANTEL

CLEARANCES

G
12
10
8
6
18
12" Mantel
16
47"
(1194mm)
14
to ceiling
12
10
17"
8
6
4
2
0
20"
to floor
Due to the extreme heat this fi replace emits,
the mantel clearances are critical.
Note: A non-combustible mantel may be
installed at a lower height if the framing
is made of metal studs covered with a
non-combustible board.
Mantel can be installed anywhere in shaded area
or higher using the above scale.
Note: Ensure the paint that is used on the
mantel and the facing is "heat resistant"
or the paint may discolour.
U32SE-5 FPI Direct Vent Gas Insert

GAS CONNECTION

GAS CONNECTION WARNING:
Only persons licensed to work with
gas piping may make the necessary
0
4
2
1) If the appliance is to be installed into an existing
chimney system, thoroughly clean the masonry
3-1/2"
or factory built fi replace.
Mantel
2) The appliance is provided with an opening on
the left hand side of the control compartment.
A 3/8" NPT gas supply pipe must be brought
near this inlet hole.
3) Locate the center point where the vent will pass
13"
through the chimney above the appliance. Move
the appliance into the exact location where it is
to be installed. Ensure that the Insert is level.
Top of
Unit
Side View
Gas
Inlet
THE APPLIANCE MUST NOT BE
CHIMNEY FLUE SERVING A
SEPARATE SOLID FUEL
This appliance is designed to be attached to two
3" (76mm) co-linear aluminium fl ex running the full
length of the chimney. The fl ue length must be a
minimum length of 8 ' (2.44m) and a maximum of 35'
(10.7m). See chart below for minimum distances from
roof. Periodically check that the vent is unrestricted.
Masonry chimneys may take various contours which
the fl exible liner will accommodate. However, keep
the fl exible liner as straight as possible, avoid
unnecessary bending.
The Air Intake pipe must be attached to the inlet air
collar of the termination cap.
Part #
948-305
946-529
gas connections
to this appliance.
C L

VENTING

CONNECTED TO A
BURNING APPLIANCE.
Description
3" Flex - 35 ft.
Co-linear DV Vertical
Termination Cap
INSTALLATION
Alternate Approved Caps
46dva-VC
Vertical Termination Cap
46dva-VCH High Wind Cap
46dva-GK
3" Co-linear Adaptor with fl ashing
In areas of consistently high winds, we recommend
using the Simpson Dura-Vent System (46dva-GK
adapter and 46dva-VCH high-wind cap).
The Air Intake pipe must be attached to the inlet
air collar of the termination cap.