Regency P36-NG4 Owners & Installation Manual page 25

Zero clearance direct vent gas fireplace
Hide thumbs Also See for Regency P36-NG4:
Table of Contents

Advertisement

One 90
Option
V
A)
0' Min.
B)
1' Min.
C)
2' Min.
D)
3' Min.
E)
4' Min.
F)
5' Min.
Lengths do not include elbow indicated
For additional vertical venting with 2 x 90
One 90
Option
V
A)
0' Min.
B)
1' Min.
C)
2' Min.
D)
3' Min.
E)
4' Min.
F)
5' Min.
G)
6' Min.
H)
7' Min.
Lengths do not include elbow indicated
FPI P36-4 Zero Clearance Direct Vent Gas Fireplace
Vertical Venting with Two (2) 90
o
elbow = Two 45
o
elbows.
H
V + V1
With these options,
2' Max.
1' Min.
max. total pipe length
4' Max.
2' Min.
is 30 feet with min.
of 6 feet total vertical
5' Max.
3' Min.
and max. 8 feet total
6' Max.
4' Min.
horizontal.
7' Max.
5' Min.
Please note min. 1
8' Max.
6' Min.
foot between 90
elbows is required.
o
elbows, refer to next page.
Vertical Venting with Three (3) 90
o
o
elbow = Two 45
elbows.
H + H1
V + V1
With these options,
2' Max.
2' Min.
max. total pipe length
2' Max
3' Min.
is 30 feet with min. of
10 feet total vertical
3' Max
4' Min.
and max. 8 feet total
4' Max
6' Min.
horizontal.
5' Max
7' Min.
Please note min. 1
6' Max
8' Min.
foot between 90
elbows is required.
7' Max
9' Min.
8' Max
10' Min.
o
Elbows
V1
o
o
Elbows
V1
H1
o
INSTALLATION
V
H
V
H
25