Knowyour System Control Panel - Briggs & Stratton Generator Owner's Manual

Hide thumbs Also See for Generator:
Table of Contents

Advertisement

Available languages

Available languages

Bri_s&Stratton Power P roducts Home Generator System
Owners
Manual
B_
Stratton"
C_tro_sbyEato_'s Cu_e., Hammer
KNOWYOUR
SYSTEM
CONTROL
PANEL
Compare this Control
Panel illustration with your generator to familiarize yourself with the _ocation of these important
controls:
Circuit
Breaker
Hour Meter
Set Exercise
Switch
Diagnostic
LED
AUTO/OFF/MANUAL
Switch
15Amp
Fuse --
Protects the Home
Generator
System
DC control
circuits. If the fuse has 'blown' (melted open)
or was removed, the engine cannot crank or start. Replace
the fuse using only an identical BUS AGC
I SA fuse.
AUTO/OFF/MANUAL
Switch --This
three-position
device is the most important
control
on the system and is
used as follows:
• "AUTO"
position
is the normal operating
position. If a
utility power outage is sensed, the system will start the
generator,
let it reach stable operating
speed, then
connect generator
power to the transfer switch.When
utility power is restored, the system reconnects
utilit_
power to the transfer switch, lets the engine stabilize
internal temperatures,
shuts off the generator, and waits
for the next utility power outage.While
waiting, it
maintains battery
with trickle
charge.
• "OFF"
position
turns off running generator, takes system
out of Automatic
mode and resets any detected faults.
• "MANUAL"
position starts the engine but does not
disconnect the transfer switch from utility power. It is
used for maintenance or diagnostic functions.
Circuit
Breaker
-- Protects the system from shorts and
other over-current
conditions. Must be ON to supply
power to the Automatic Transfer Switch.
Diagnostic
LED --
Used for troubleshooting
operational
problems with the Home Generator
System.All fault
conditions are described in the section "Fault Detection
System".
Hour
Meter
--The
hour meter records the total number
of hours the generator
has been running and is used to
schedule maintenance tasks.
Set Exercise
Switch
-- Used to set the exercise cycle
start time and day-of-the-week.
Exercise cycle only occurs
in AUTO mode.