Clearances; Locating Fireplace - Empire Comfort Systems DVX36DP31(N,P)-1 Installation Instructions And Owner's Manual

Studio series direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

Clearance to Combustibles
Back
Side
Floor
Top Stand-off
Top Framing Edge
SEE MANTLE CHART FOR
MAXIMUM MANTLE DEPTH
SEE MANTLE CHART
FOR MINIMUM HEIGHT
OF MANTLE ABOVE UNIT
FINISHED WALL
(COMBUSTIBLE)
NON-COMBUSTIBLE
FIRST 6" (SEE
MAGNIFIED VIEW)
TOP FRAMING
LEDGE
GLASS FRONT
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the fireplace. The flow of heat can
ignite combustibles.
Note: Island (C) and Room Divider (F)
installation is possible as long as the
horizontal portion of the vent system
(H) does not exceed 20 feet with a
minimum vertical run of 8 feet. See
details in Venting Section.
When you install your Direct Vent
Fireplace in (F) Room divider or (A) Flat
on wall corner positions, a minimum of
6 inches clearance must be maintained
from the perpendicular wall and the
front edge of the appliance.
Page 8

CLEARANCES

0" (0 mm)
0" (0 mm)
0" (0 mm)
0" (0 mm)
6" (152 mm)
2" x 4" HEADER
STAND OFF
6" (152mm) HEIGHT
ABOVE TOP OF
FIREPLACE
6"
NAILING
FLANGES
Figure 2

LOCATING FIREPLACE

(A) CORNER
INSTALLATION
(E) ANGLED CORNER
Mantel Chart (Figure 3)
19"
TOP EDGE OF FIREPLACE
Clearances (Figure 4)
Clearance from top front edge of fireplace to ceiling is 36"
Clearance from side of fireplace to adjacent sidewall is 6".
(C) ISLAND
INSTALLATION
INSTALLATION
Figure 5
12" (305mm)
10" (254mm)
MANTEL
COMBUSTIBLE TRIM AND
8"
MANTELS ALLOWED IN
SHADED AREA
6"
4 1/2"
3 3/4"
3"
18 3/4"
2 1/4"
1 1/2"
17"
16"
3/4"
15"
14"
13"
12"
11"
10"
Figure 3
36"
(914mm)
Figure 4
(B) CABINET
INSTALLATION
(D) FLUSH WALL
INSTALLATION
(F) ROOM DIVIDER
INSTALLATION
25613-0-0309