Empire Comfort Systems DVX36DP31(N,P)-1 Installation Instructions And Owner's Manual page 12

Studio series direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

Flush Wall Installation
FINISHED WALL
6" OF NON-COMBUSTIBLE MATERIAL
NON-COMBUSTIBLE MATERIAL
(INSTALLATION IS OPTIONAL
Combustible Surround Installation
2 X 4
HEADER
STAND OFF
Page 12
JOINT BETWEEN FINISHED
WALL AND UNIT SEALED
WITH 300° F, 149° C SEALANT
MATERIAL (SEALANT IS OPTIONAL)
Figure 12
MANTELSHELF
COMBUSTIBLE SURROUND
FINISHED WALL
6" OF NON-COMBUSTIBLE
MATERIAL
FRONT TRIM OR
NON-COMBUSTIBLE
MATERIAL (INSTALLATION
IS OPTIONAL)
JOINT BETWEEN FINISHED
WALL AND UNIT SEALED WITH
300°F (149°C) SEALANT MATERIAL
(SEALANT IS OPTIONAL)
Figure 13
Attention: Cold climate installation recommendation:
When installing this unit against a non-insulated exterior
wall, it is recommended that the outer walls be insulated to
conform to applicable insulation codes.
Vent Runs (Figures 14, 15, and 16)
In planning the installation for the fireplace, it is necessary to install
certain components before the appliance is completely positioned
and installed. These include the direct vent system, gas piping for
the appliance and the electrical wiring.
The appliance can be mounted on any of the following surfaces:
1. A flat, hard combustible (burnable) surface.
2. A raised wooden platform.
3. Four (4) corner supports. (Example: Four (4) concrete masonry
blocks.) These supports must be positioned so they contact all
four (4) perimeter edges on the bottom of the unit.
VERTICAL, 90° ELBOW WITH HORIZONTAL
TERMINATION
DVX36,42
50 1/2" (1283mm)
TO BOTTOM
OF UNIT
3" (76mm)
MINIMUM CLEARANCE
TO COMBUSTIBLES
VENT CAP/
THIMBLE
WALL FIRESTOP
Figure 14
25613-0-0309