Note
Under the condition that the drive system was commissioned with STARTER and no
PROFIdrive telegram was activated, the infeed can be powered-up by issuing an enable
signal at the EP terminals and a positive signal edge at OFF1 (p0840).
Switching off the Smart Line Module
To switch off the Active Line Module, carry out the steps for switching it on in reverse order.
Switching off the controller with the OFF1 signal is delayed by the time entered in p3490.
This allows the attached drives to be braked in a controlled manner.
Control and status messages
Table 1-5
Smart Infeed open-loop control
Signal name
ON/OFF1
OFF2
Enable operation
Inhibit regenerating
Acknowledge error
Master ctrl by PLC
Table 1-6
Smart Infeed status message
Signal name
Ready to power up
Ready to run
Operation enabled
Fault active
No OFF2 active
Power-on disable
Alarm present
Master ctrl by PLC
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Internal control word
STWAE.0
STWAE.1
STWAE.3
STWAE.6
STWAE.7
STWAE.10
Internal status
word
ZSWAE.0
ZSWAE.1
ZSWAE.2
ZSWAE.3
ZSWAE.4
ZSWAE.6
ZSWAE.7
ZSWAE.9
Binector input
Display of internal
p0840 ON/OFF1
r0898.0
p0844 1 OFF2 and
p0845 2 OFF2
p0852 Enable
operation
p3533 Inhibit
regenerating
p2103 1 Acknowledge
or
p2104 2 Acknowledge
or
p2105 3 Acknowledge
p0854 Master ctrl by
PLC
Parameter
r0899.0
r0899.1
r0899.2
r2139.3
r0899.4
r0899.6
r2139.7
r0899.9
PROFIdrive telegram 370
control word
A_STW1.0
r0898.1
A_STW1.1
r0898.3
A_STW1.3
r0898.6
A_STW1.6
r2138.7
A_STW1.7
r0898.10
A_STW1.10
PROFIdrive telegram 370
A_ZSW1.0
A_ZSW1.1
A_ZSW1.2
A_ZSW1.3
A_ZSW1.4
A_ZSW1.6
A_ZSW1.7
A_ZSW1.9
Infeed
1.2 Smart Infeed